Inspections for the day of: Thursday, May 18, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00140 INSP-Final Inspection5/16/20065/18/20065/18/2006 4:03:12 PMPPART
Fire sprinkler for the west half of the remodel area under the scope of work passed final inspection.
FIR06-00285 INSP-Sprinkler Rough-in5/17/20065/18/20065/18/2006 3:14:21 PMPPART
Overhead sprinkler rough-in inspection for cover is satisfactory except one room at the NW corner which is overspaced per design limitations, also need to provide plans reflecting changed wall locations and added/deleted heads at various locations where different from approved drawings.
FIR06-00199 INSP-Final Inspection5/17/20065/18/20065/18/2006 2:40:41 PMPPART
Fire alarm testing for the area of remodel designated as phase one is acceptable as marked on approved plans, one duct detector has the sample and vent tubes installed backward, need to test the manual pull at the nurses station, will verify these items at next inspection for the remainder of the project scope.
BLD06-00317 FIRE-Final Inspection5/17/20065/18/20065/18/2006 11:01:50 AMAPART
Life safety inspection for the west half of the floor remodel is acceptable.
FIR06-00258 INSP-Alarm Testing5/15/20065/18/20065/18/2006 11:00:28 AMAPART
Alarm tested satisfactory for the west portion of the project, need to add one notification device at area lacking coverage as marked on approved plans, the remainder of alarm work for the east half of the floor is not yet completed.
FIR06-00331 INSP-Final Inspection5/16/20065/18/20065/18/2006 9:20:18 AMAFAIL
Electrical power failed to shut down upon activation of the hood suppression system, "blow off" test and the manual pull tested satisfactory. Need to relocate the K class extinguisher a min. of 10' feet from the cooking appliances.