BLD06-03238
| FIRE-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 4:13:40 PM | P | CANC |
|
|
This needs to be rescheduled per Mike.
|
FIR07-00139
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 4:12:16 PM | P | PASS |
|
|
permit finaled
|
FIR07-00139
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 4:09:30 PM | P | CANC |
|
|
Needs to be rescheduled.
|
FIR07-00379
| INSP-Sprinkler Rough-in | 5/18/2007 | 5/18/2007 | 5/18/2007 4:03:21 PM | P | CANC |
|
|
No time for inspection today. To be rescheduled
|
FIR06-00558
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 4:02:34 PM | P | PASS |
|
|
permit finaled
|
BLD07-00332
| FIRE-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 2:53:33 PM | P | PASS |
|
|
life safety passed.
|
FIR06-00770
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 2:44:07 PM | P | PASS |
|
|
Permit finaled
|
BLD07-00951
| FIRE-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 2:28:57 PM | A | CANC |
|
|
Duplicate inspection. See entry for afternoon.
|
BLD06-02665
| FIRE-Final Inspection | 5/17/2007 | 5/18/2007 | 5/18/2007 2:27:56 PM | A | FAIL |
|
|
Provide plans for the shell permit and do inspection, final sprinkler permit, repair the exit discharge lighting on the front single man door exits and provide the occupant load signs as discussed.
|
FIR06-00978
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 2:16:45 PM | P | PASS |
|
|
Permit finaled
|
FIR06-01002
| INSP-Final Inspection | 5/17/2007 | 5/18/2007 | 5/18/2007 1:54:01 PM | A | FAIL |
|
|
The singel pendant installed in the back dressing room is standard instead of quick responce
|
BLD07-00951
| FIRE-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 1:47:15 PM | P | FAIL |
|
|
The electrician was still in the process of installing exit signs and emergency lights. Everything else appeared to be ok.
|
FIR07-00190
| INSP-Alarm Testing | 5/17/2007 | 5/18/2007 | 5/18/2007 12:56:22 PM | A | PASS |
|
|
Permit finaled
|
BLD07-00391
| FIRE-Final Inspection | 5/17/2007 | 5/18/2007 | 5/18/2007 12:54:01 PM | A | PASS |
|
|
life safety passed.
|
FIR07-00308
| INSP-Final Inspection | 5/18/2007 | 5/18/2007 | 5/18/2007 11:41:10 AM | P | PASS |
|
|
permit finaled
|
FIR07-00282
| INSP-Final Inspection | 5/17/2007 | 5/18/2007 | 5/18/2007 9:44:08 AM | A | PASS |
|
|
permit finaled
|
FIR07-00258
| INSP-Alarm Testing | 5/17/2007 | 5/18/2007 | 5/18/2007 9:11:39 AM | A | FAIL |
|
|
The first induct detector we tried to test did not operate the fire smoke damper. No other items were tested.
|