Inspections for the day of: Friday, May 18, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03238 FIRE-Final Inspection5/18/20075/18/20075/18/2007 4:13:40 PMPCANC
This needs to be rescheduled per Mike.
FIR07-00139 INSP-Final Inspection5/18/20075/18/20075/18/2007 4:12:16 PMPPASS
permit finaled
FIR07-00139 INSP-Final Inspection5/18/20075/18/20075/18/2007 4:09:30 PMPCANC
Needs to be rescheduled.
FIR07-00379 INSP-Sprinkler Rough-in5/18/20075/18/20075/18/2007 4:03:21 PMPCANC
No time for inspection today. To be rescheduled
FIR06-00558 INSP-Final Inspection5/18/20075/18/20075/18/2007 4:02:34 PMPPASS
permit finaled
BLD07-00332 FIRE-Final Inspection5/18/20075/18/20075/18/2007 2:53:33 PMPPASS
life safety passed.
FIR06-00770 INSP-Final Inspection5/18/20075/18/20075/18/2007 2:44:07 PMPPASS
Permit finaled
BLD07-00951 FIRE-Final Inspection5/18/20075/18/20075/18/2007 2:28:57 PMACANC
Duplicate inspection. See entry for afternoon.
BLD06-02665 FIRE-Final Inspection5/17/20075/18/20075/18/2007 2:27:56 PMAFAIL
Provide plans for the shell permit and do inspection, final sprinkler permit, repair the exit discharge lighting on the front single man door exits and provide the occupant load signs as discussed.
FIR06-00978 INSP-Final Inspection5/18/20075/18/20075/18/2007 2:16:45 PMPPASS
Permit finaled
FIR06-01002 INSP-Final Inspection5/17/20075/18/20075/18/2007 1:54:01 PMAFAIL
The singel pendant installed in the back dressing room is standard instead of quick responce
BLD07-00951 FIRE-Final Inspection5/18/20075/18/20075/18/2007 1:47:15 PMPFAIL
The electrician was still in the process of installing exit signs and emergency lights. Everything else appeared to be ok.
FIR07-00190 INSP-Alarm Testing5/17/20075/18/20075/18/2007 12:56:22 PMAPASS
Permit finaled
BLD07-00391 FIRE-Final Inspection5/17/20075/18/20075/18/2007 12:54:01 PMAPASS
life safety passed.
FIR07-00308 INSP-Final Inspection5/18/20075/18/20075/18/2007 11:41:10 AMPPASS
permit finaled
FIR07-00282 INSP-Final Inspection5/17/20075/18/20075/18/2007 9:44:08 AMAPASS
permit finaled
FIR07-00258 INSP-Alarm Testing5/17/20075/18/20075/18/2007 9:11:39 AMAFAIL
The first induct detector we tried to test did not operate the fire smoke damper. No other items were tested.