Inspections for the day of: Wednesday, May 18, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00174 INSP-Final Inspection5/17/20115/18/20115/19/2011 5:28:48 PMAFAIL
Ref. activity notes dated 5/17.
FIR11-00176 INSP-Final Inspection5/17/20115/18/20115/19/2011 5:24:15 PMAFAIL
Noted items include: incorrect or insufficient visual coverage at six locations due to cd settings on notification appliances which do not correlate with the plans, several wall mounted notification appliances along the length of the recieving/stock isles are beyond specified mounting heights allowed per NFPA 72 unless stipulations of the performance-based alternative can be met and documentation provided per conditions of the standard, noted four locations lacking visual coverage including the pharmacy waiting area, pharmacy patient consultation, bakery sales and bakery prep., need to verify db levels are met at the meat prep. room and the mech.areas. Pharmacy RR and the bank tenant space are not accessible for testing prior to 9:30 AM.
BLD11-00298 FIRE-Final Inspection5/18/20115/18/20115/18/2011 3:27:48 PMPPART
FIR11-00135 INSP-Final Inspection5/18/20115/18/20115/18/2011 3:27:03 PMPPART
Final pending drop ceiling at the electrical/comm closet.
BLD10-02790 FIRE-Conference5/18/20115/18/20115/18/2011 3:25:30 PMPDONE
Regarding project related FIR permit work.
FIR11-00175 INSP-Final Inspection5/17/20115/18/20115/18/2011 3:24:23 PMAPEND
Scheduled in conjunction with Life safety final Phone #: ###-#### >> Inspection requested via web by Wayne Berry
BLD11-00683 FIRE-Final Inspection5/17/20115/18/20115/18/2011 3:23:55 PMANR
Life safety / Will also call for FS Final in conjunction! Phone #: ###-#### >> Inspection requested via web by Wayne Berry *Note- pending door install
FIR11-00192 INSP-Final Inspection5/17/20115/18/20115/18/2011 3:22:09 PMAPASS
Fire sprinkler work passed both rough-in and final inspections. Permit finaled.
FIR11-00191 INSP-Final Inspection5/17/20115/18/20115/18/2011 3:21:02 PMAPASS
Fire alarm test passed. Permit finaled.