ELE13-00084
| ELE-Aging Inspection | 5/18/2015 | 5/18/2015 | 5/20/2015 12:25:11 PM | | DONE |
|
|
Still under construction
|
ELE15-01286
| Final | 5/18/2015 | 5/18/2015 | 5/18/2015 4:24:45 PM | P | PASS |
|
|
We are requesting a final inspection for today in the afternoon. Our contact is Alex ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate Final ok
|
ELE14-03524
| Electrical Rough-In | 5/18/2015 | 5/18/2015 | 5/18/2015 3:43:23 PM | P | PASS |
|
|
would like call ahead; Tyler Phone #: ###-#### Master Bath and smoke detectors rough in ok cover
|
ELE15-00517
| Final | 5/18/2015 | 5/18/2015 | 5/18/2015 3:23:14 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean 314.25- All boxes shall be covered. open junction box, termination not complete end of hall. 110.26- low volt rack in front of panel unable to check
|
ELE15-00410
| Final | 5/18/2015 | 5/18/2015 | 5/18/2015 2:49:38 PM | P | PASS |
|
|
Treon Phone #: ###-#### Final ok
|
ELE15-01301
| Electrical Rough-In | 5/18/2015 | 5/18/2015 | 5/18/2015 2:11:53 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Nurses station rough in ok cover
|
ELE15-00838
| Final | 5/15/2015 | 5/18/2015 | 5/18/2015 1:47:36 PM | P | FAIL |
|
|
Please call 30 minutes or so in advance so I can meet you there and let you in. Thanks. Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester 314.25- All boxes shall have covers. 406.12(A)- All 15 and 20 amp 120 volt receptacle outlets installed in a dwelling unit shall be tamper resistant type.
|
ELE14-02747
| Final | 5/18/2015 | 5/18/2015 | 5/18/2015 1:25:06 PM | P | PASS |
|
|
Mike Phone #: ###-#### Electrical complete Final ok
|
ELE15-01181
| Final | 5/18/2015 | 5/18/2015 | 5/18/2015 12:45:32 PM | P | NR |
|
|
Garage code 0500 Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Contractor requested wrong address will reschedule
|
ELE15-01328
| Electrical Rough-In | 5/15/2015 | 5/18/2015 | 5/18/2015 10:11:43 AM | A | FAIL |
|
|
Angela Phone #: ###-#### 300.4- NM cable shall be protected from physical damage when ran thru bored holes that do not maintain 1 1/4" from framing surface. NM cable shall be secured 1 1/4" from framing surface. BCC- Make up shall be complete. Tie ground thru with pigtails for each device and neutrals in switch boxes.
|
ELE15-01286
| Final | 5/15/2015 | 5/18/2015 | 5/18/2015 9:31:42 AM | A | NR |
|
|
We are requesting a final inspection for Monday 5/18/15 in the AM. Our onsite contact is Alex ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate Contractor will reschedule
|
ELE15-01432
| Final | 5/15/2015 | 5/18/2015 | 5/18/2015 9:22:24 AM | A | PASS |
|
|
Bill Phone #: ###-#### Final ok
|
ELE15-01432
| Permanent Service | 5/18/2015 | 5/18/2015 | 5/18/2015 9:21:58 AM | P | PASS |
|
|
Bill Phone #: ###-#### Unit 102 p/s u/g rec ok
|
ELE15-01382
| Rough-In Permanent Service | 5/17/2015 | 5/18/2015 | 5/18/2015 9:03:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
ELE15-01002
| Electrical Rough-In | 5/18/2015 | 5/18/2015 | 5/18/2015 8:49:50 AM | A | PASS |
|
|
This is a ceiling inspection. Please call Kyle at ###-#### 30 mins. prior to arrival. Thx. Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Grid rough in ok cover
|