Inspections for the day of: Thursday, May 18, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-01244 FIRE-Final Inspection5/17/20175/18/20175/18/2017 2:20:31 PMAFAIL
Need the flash lights as discussed for the emergency lighting and the fire extinguisher given its annual inspection
BLD17-01447 FIRE-Final Inspection5/18/20175/18/20175/18/2017 1:57:49 PMPFAIL
Provide fire extinguisher as discussed and the occupant load sign
FIR17-00235 INSP-Final Inspection5/18/20175/18/20175/18/2017 1:51:45 PMPPART
A temporary is being given with Scott's permission until the FIR is submitted/issued/tested for the hood suppression interconnection with the existing fire alarm system. Today I verified that the hood suppression shut down the gas and electrical.
FIR16-00738 INSP-Sprinkler Rough-in5/18/20175/18/20175/18/2017 12:46:35 PMPPASS
The two rooms that had been covered prior to a tenting inspection are now approved for cover
BLD17-00277 FIRE-Final Inspection5/17/20175/18/20175/18/2017 9:58:47 AMAPASS
life safety passed
FIR17-00140 INSP-Final Inspection5/17/20175/18/20175/18/2017 9:21:17 AMAPASS
permit finaled
FIR17-00097 INSP-Sprinkler Rough-in/Hydro5/17/20175/18/20175/18/2017 9:20:25 AMAPASS
24 hour air test for the dry system passed
FIR16-00738 INSP-Sprinkler Rough-in/Hydro5/17/20175/18/20175/18/2017 9:19:24 AMAPASS
24 hr air test for the dry system passed