Inspections for the day of: Friday, May 18, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01789 Electrical Rough-In5/17/20185/18/20185/18/2018 2:43:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley
Basement to be unfinished, main level rough in ok cover
ELE18-01888 Final5/18/20185/18/20185/18/2018 2:02:31 PMPPASS
call 30 mintues before to meet // Warren Phone #: ###-#### Final ok
ELE18-01888 Electrical Rough-In5/18/20185/18/20185/18/2018 1:56:59 PMPPASS
call 30 mintues before to meet // Warren Phone #: ###-####
Change out misc switches and wiring fished in walls for receptacles. Rough in ok
ELE18-01498 Electrical Rough-In5/18/20185/18/20185/18/2018 1:27:37 PMPPASS
Ceiling Rough-In Inspection

Contact is Brice Thorpe

Thank you ; have a great weekend! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Grid rough in ok cover
ELE18-01499 Electrical Rough-In5/18/20185/18/20185/18/2018 1:27:08 PMPPASS
Ceiling Rough On Inspection

Contact is Bruce Thorpe

Thank you ; have a lovely afternoon Phone #: ###-#### Inspection via web by JENNY EMEL Grid rough in ok cover
ELE18-00550 Final5/17/20185/18/20185/18/2018 12:37:55 PMAPASS
Will need 30 min notice prior to arrival Final ok
ELE18-01753 Rough-In Permanent Service5/17/20185/18/20185/18/2018 11:50:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE18-01867 Rough-In Permanent Service5/17/20185/18/20185/18/2018 11:25:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-00538 Final5/17/20185/18/20185/18/2018 10:47:50 AMAFAIL
garage code 3824 Phone #: ###-#### Inspection requested via web by Darryn Coburn
210.52- A receptacle outlet shall be located with in 6' of master patio door.
Spark ring needed receptacle below TV location.
422.31, 110.3- Furnace shall have a disconnecting means with in site of unit as per manufacturers instructions.
ELE18-00612 Final5/17/20185/18/20185/18/2018 10:43:44 AMAFAIL
garage code 3924 Phone #: ###-#### Inspection requested via web by Darryn Coburn
210.52- A receptacle outlet shall be located with in 6' of master patio door.
422.30, 110.3- Furnace shall have a disconnecting means with in site of unit as per manufacturers instructions. Microwave shall have a readily accessible disconnecting means.
ELE18-01874 Permanent Service5/17/20185/18/20185/18/2018 9:12:09 AMAPASS
service for cable tv power supply, alta cabinet, accessed off of Fairview, to Eldorado, then Camelot. Call for access - Andy Phone #: ###-####
Recall when energized so can check receptacles. p/s u/g n ok