FIR17-00694
| INSP-Sprinkler Rough-in | 5/17/2018 | 5/18/2018 | 5/18/2018 2:56:29 PM | P | PART |
|
|
Rough in inspection for overhead fire sprinkler piping complete, rough in inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover. Notated city approved drawings where sway brace corrections are required.
The phone number provided is for Tom with CM Company. Our foreman on site is Troy, but he does not have a cell phone at the moment. Our office number is ###-#### if you have questions. Thank you! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-00972
| FIRE-Final Inspection | 5/18/2018 | 5/18/2018 | 5/18/2018 2:53:34 PM | P | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
Jade Phone #: ###-####
|
FIR18-00090
| INSP-Sprinkler Rough-in | 5/18/2018 | 5/18/2018 | 5/18/2018 11:11:16 AM | P | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping in south open office area complete, complete area of work approved for cover.
Jordan Phone #: ###-####
|
FIR18-00299
| INSP-Sprinkler Rough-in | 5/18/2018 | 5/18/2018 | 5/18/2018 11:10:08 AM | A | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping in area of work complete, approved for cover.
Javier Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR18-00125
| INSP-Sprinkler Rough-in | 5/18/2018 | 5/18/2018 | 5/18/2018 11:09:27 AM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping partially complete, heads for elevator shaft to be installed at a later date, remaining pipin approved for cover.
. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00125
| INSP-Sprinkler Rough-in/Hydro | 5/17/2018 | 5/18/2018 | 5/18/2018 11:08:34 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00086
| INSP-Final Inspection | 5/17/2018 | 5/18/2018 | 5/18/2018 9:54:02 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Sean. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD18-00828
| FIRE-Final Inspection | 5/17/2018 | 5/18/2018 | 5/18/2018 12:00:00 AM | A | CANC |
|
|
Mike Phone #: ###-####
|