Inspections for the day of: Monday, May 18, 2020.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-01747 Rough-in5/18/20205/18/20205/18/2020 4:15:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Arcadio Martinez
- R/I ok furnace coil in crawl
MEC20-01747 Pressure Test5/18/20205/18/20205/18/2020 4:14:11 PMPPASS
Phone #: ###-#### Inspection requested via web by Arcadio Martinez
- 20lb gas test ok
MEC20-01366 Pressure Test5/18/20205/18/20205/18/2020 3:37:44 PMPPASS
please call jimmy prior to arrival for access Phone #: ###-#### Inspection requested via web by Nicholas Paige
- 20lb gas test ok to meter location
MEC20-01366 Rough-in5/18/20205/18/20205/18/2020 3:37:15 PMPPASS
please call jimmy prior to arrival for access Phone #: ###-#### Inspection requested via web by Nicholas Paige
- R/I duct seal ok for insulation
MEC20-00571 Rough-in5/18/20205/18/20205/18/2020 3:01:56 PMPPART
Phase 2 seal and fire caulk inside of vent shaft. Inspection requested via web by yuriy kryachun
- units 240,241 first layer sheetrock and fire caulk ok
-units 330-341 first layer sheetrock and fire caulk ok
MEC20-01562 Rough-in5/18/20205/18/20205/18/2020 2:42:35 PMPPART
Mechanical Duct Seal Inspection needed at Cafe Rio If you have any questions please contact Karl ###-####,Thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin
- partial R/I duct seal ok for insulation
MEC20-01928 Final5/17/20205/18/20205/18/2020 2:24:28 PMPNR
Please call Chris Mato''s prior to arrive to ensure ready for inspection. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
MEC20-01928 Pressure Test5/17/20205/18/20205/18/2020 2:24:18 PMPNR
Please call Chris Mato''s prior to arrive to ensure ready for inspection. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
MEC20-01814 Final5/14/20205/18/20205/18/2020 2:04:42 PMPPASS
Please call Bill Henning at least 30 mins out. Thank you! Phone #: ###-#### Inspection requested via web by Denise Colin
- final ok
MEC20-01865 Pressure Test5/15/20205/18/20205/18/2020 1:36:26 PMPFAIL
Phone #: ###-#### Inspection requested via web by Matt Jones
- gas line has a small leak somewhere in system. check for leaks and retest.
MEC20-01352 Final5/13/20205/18/20205/18/2020 1:02:46 PMPPASS
Please call Rob Caron prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- final ok
MEC20-01911 Rough-in5/15/20205/18/20205/18/2020 10:05:44 AMAFAIL
access code for entry 1987 Phone #: ###-#### Inspection requested via web by Angie Maguire
- approved man J
- 2 5lb flue tests failed
- line set insulation need repaired in crawl
-dryer vent needs installed in 2x6 wall
- duct seal upstairs
- supply trunk in crawl needs insulated by final
MEC20-01910 Rough-in5/15/20205/18/20205/18/2020 9:55:12 AMAFAIL
access code for entry 1987 Phone #: ###-#### Inspection requested via web by Angie Maguire
-approved man j
- 2 5lb flue test failed
- line set insulation needs repaired in crawl
- supply trunk in attic is smashed re route
-duct seal upstairs
- supply trunk in crawl needs insulated by final
MEC20-01911 Pressure Test5/15/20205/18/20205/18/2020 9:52:07 AMAFAIL
access code for entry 1987 Phone #: ###-#### Inspection requested via web by Angie Maguire
2- 5lb flue test fail
- 20lb gas test ok
-tagged meter location
MEC20-01910 Pressure Test5/15/20205/18/20205/18/2020 9:50:39 AMAFAIL
access code for entry 1987 Phone #: ###-#### Inspection requested via web by Angie Maguire
2- 5lb flue tests fail
- 20lb gas test ok
- tagged meter location
MEC20-00136 Final5/15/20205/18/20205/18/2020 9:02:51 AMAPASS
Homeowner works from home. Please call on way: Richard ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- final ok
MEC20-01780 Final5/14/20205/18/20205/18/2020 8:56:24 AMAPASS
Please call the tenant when on way: Dani ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- A/C coil co ok
MEC19-01831 Mec-Aging Inspection5/18/20205/18/20205/18/2020 8:19:28 AM PASS
Doc Permit Expired ok
MEC19-01831 DOC - Permit Expired5/18/20205/18/20205/18/2020 8:19:14 AMAPASS
Doc Permit Expired ok not active
MEC19-03378 Mec-Aging Inspection5/18/20205/18/20205/18/2020 8:18:51 AM PASS
Doc Permit Expired ok
MEC19-03378 DOC - Permit Expired5/18/20205/18/20205/18/2020 8:18:38 AMAPASS
Doc Permit Expired ok not active