FIR03-00071
| INSP-Supply line flush | 5/18/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 5/18/2003 at 12:41:44 PM. Contact: ###-####. hydro on UG and FDC okay; man hole is installed for the FDC - will need to verify drain and ball drip installed 5/19/2003 10:01:57 AM
|
FIR03-00152
| INSP-Sprinkler Rough-in/Hydro | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | A | PART |
|
|
hydro on dry system okay; will need detail for hangers on TJI's for the six inch main
|
BLD02-01912
| FIRE-Final Inspection | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | FAIL |
|
|
alarms and fire sprinklers okay; smoke vents won't open
|
FIR02-00436
| INSP-Final Inspection | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | PASS |
|
|
|
FIR03-00041
| INSP-Final Inspection | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | PASS |
|
|
|
FIR01-00462
| INSP-Sprinkler Rough-in | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | PART |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore storage in fellowship hall to be below 18 inches (storage room); heads under stage - need to prevent mechanical damage from sliding in table racks 5/19/2003 3:47:57 PM
|
FIR02-00350
| INSP-Alarm Testing | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | CANC |
|
|
Daniel Buccino; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino rescheduled for 5/20 per Dan 5/19/2003 4:12:50 PM
|
FIR02-00329
| INSP-Alarm Testing | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | CANC |
|
|
daniel; Phone #: ###-#### Internet Inspection Request from: Darla Downs rescheduled for 5/20 per Dan 5/19/2003 4:12:33 PM
|
FIR03-00174
| INSP-Sprinkler Rough-in/Hydro | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | PART |
|
|
This is for your walkthrough that you performed on friday; Phone #: ###-#### Internet Inspection Request from: Trent Bice flange fitting at UG connection to meet NFPA 13 Table 3-5.1; r/i okay 5/19/2003 12:25:57 PM
|
FIR03-00089
| INSP-Sprinkler Rough-in | 5/19/2003 | 5/19/2003 | 5/19/2003 12:00:00 AM | P | PART |
|
|
###-#### UG cover okay; still need flush and hydro 5/19/2003 12:24:26 PM
|