Inspections for the day of: Monday, May 19, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00071 INSP-Supply line flush5/18/20035/19/20035/19/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 5/18/2003 at 12:41:44 PM. Contact: ###-####. hydro on UG and FDC okay; man hole is installed for the FDC - will need to verify drain and ball drip installed 5/19/2003 10:01:57 AM
FIR03-00152 INSP-Sprinkler Rough-in/Hydro5/19/20035/19/20035/19/2003 12:00:00 AMAPART
hydro on dry system okay; will need detail for hangers on TJI's for the six inch main
BLD02-01912 FIRE-Final Inspection5/19/20035/19/20035/19/2003 12:00:00 AMPFAIL
alarms and fire sprinklers okay; smoke vents won't open
FIR02-00436 INSP-Final Inspection5/19/20035/19/20035/19/2003 12:00:00 AMPPASS
FIR03-00041 INSP-Final Inspection5/19/20035/19/20035/19/2003 12:00:00 AMPPASS
FIR01-00462 INSP-Sprinkler Rough-in5/19/20035/19/20035/19/2003 12:00:00 AMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore storage in fellowship hall to be below 18 inches (storage room); heads under stage - need to prevent mechanical damage from sliding in table racks 5/19/2003 3:47:57 PM
FIR02-00350 INSP-Alarm Testing5/19/20035/19/20035/19/2003 12:00:00 AMPCANC
Daniel Buccino; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino rescheduled for 5/20 per Dan 5/19/2003 4:12:50 PM
FIR02-00329 INSP-Alarm Testing5/19/20035/19/20035/19/2003 12:00:00 AMPCANC
daniel; Phone #: ###-#### Internet Inspection Request from: Darla Downs rescheduled for 5/20 per Dan 5/19/2003 4:12:33 PM
FIR03-00174 INSP-Sprinkler Rough-in/Hydro5/19/20035/19/20035/19/2003 12:00:00 AMPPART
This is for your walkthrough that you performed on friday; Phone #: ###-#### Internet Inspection Request from: Trent Bice flange fitting at UG connection to meet NFPA 13 Table 3-5.1; r/i okay 5/19/2003 12:25:57 PM
FIR03-00089 INSP-Sprinkler Rough-in5/19/20035/19/20035/19/2003 12:00:00 AMPPART
###-#### UG cover okay; still need flush and hydro 5/19/2003 12:24:26 PM