Inspections for the day of: Thursday, May 19, 2005.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02154 FIRE-Final Inspection5/18/20055/19/20055/19/2005 10:19:46 AMAFAIL
Provide approved hardware on door to customer pick up area. Lower three provided fire ext. to no higher than 48" above floor. Verify proper hardware on two sets of double doors at exits from greenhouse when installed. Remove exit sign at door to cust
FIR05-00045 INSP-Sprinkler Rough-in5/19/20055/19/20055/19/2005 12:00:00 AMPCANC
please call 30 min prior to inspection//tom; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa///cancel per tom easton 5/19/05 12:20pm BAS
FIR05-00045 INSP-Sprinkler Rough-in5/19/20055/19/20055/19/2005 12:00:00 AMPPART
Underground fire supply line stub out OK to cover.
FIR05-00045 INSP-Conference5/19/20055/19/20055/19/2005 12:00:00 AMPDONE
On site discussion with Tom Easton of Grinnell regarding sprinkler coverage requirements in concealled spaces above awning. Spoke with Bill Alexander regarding this issue and concluded sprinklers are required.