ELE08-01268
| Permanent Service | 5/19/2008 | 5/19/2008 | 5/19/2008 4:41:43 PM | P | FAIL |
|
|
corr. called 110.26(F)(2) remove tree clearence for p/s, 250.92(A) bond steel raceway bottom of p/s meter side, 110.3, remove losd side feeder ser cable from meter side of service gear 310.16 shall protect #12 feeder to a/c at 20 amps not 30 check 4wire brach circuits for range abd dryer, remove old GEC you have a the new one did not have access to inside house could not check subpanel or grds or bonds to water
|
ELE08-01298
| Temporary Service | 5/19/2008 | 5/19/2008 | 5/19/2008 3:21:43 PM | P | PASS |
|
|
david Phone #: ###-#### t/s u/g new ok
|
ELE08-01261
| Permanent Service | 5/16/2008 | 5/19/2008 | 5/19/2008 1:50:08 PM | P | NR |
|
|
Pump Service Inspection. Please call Eddy at ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Jeff Durham called
|
ELE08-01295
| Permanent Service | 5/19/2008 | 5/19/2008 | 5/19/2008 1:07:38 PM | P | FAIL |
|
|
Permanent pole for emissions test company Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called corr. posted250.24(A)(1) shall terminate GEC at neutral bus, 110.12(C) clean p/s of dirt and junk
|
ELE07-03859
| Final | 5/19/2008 | 5/19/2008 | 5/19/2008 12:14:43 PM | P | FAIL |
|
|
Must call Toby @ ###-#### 1/2 hour prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called still needs to remove GEC from raceways and boxes 250.64(E) & 250.92(A)(3)
|
ELE07-03859
| Final | 5/16/2008 | 5/19/2008 | 5/19/2008 10:24:12 AM | A | NH |
|
|
Final Inspection. David Luke Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson no access talked to parks person
|
ELE08-00506
| Electrical Rough-In | 5/19/2008 | 5/19/2008 | 5/19/2008 9:56:44 AM | A | PART |
|
|
din rm grid ceiling ok
|
ELE08-00506
| Final | 5/19/2008 | 5/19/2008 | 5/19/2008 9:14:48 AM | A | CANC |
|
|
ceiling inspection for cover in the dinning area Phone #: ###-#### Internet Inspection Request from: Spencer Mclean see added r/i
|
ELE08-01120
| Permanent Service | 5/15/2008 | 5/19/2008 | 5/19/2008 9:12:48 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty p/s u/g new for meter
|
ELE08-00745
| Electrical Rough-In | 5/16/2008 | 5/19/2008 | 5/19/2008 8:49:44 AM | A | CANC |
|
|
tom Phone #: ###-#### e grid coverd eleectrical contr , and pool contr responsible for grid
|
ELE08-01273
| Electrical Rough-In | 5/16/2008 | 5/19/2008 | 5/19/2008 8:08:07 AM | A | PART |
|
|
Greg, please call 30 minutes prior Phone #: ###-#### done by 370 friday
|