Inspections for the day of: Monday, May 19, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01268 Permanent Service5/19/20085/19/20085/19/2008 4:41:43 PMPFAIL
corr. called 110.26(F)(2) remove tree clearence for p/s, 250.92(A) bond steel raceway bottom of p/s meter side, 110.3, remove losd side feeder ser cable from meter side of service gear 310.16 shall protect #12 feeder to a/c at 20 amps not 30 check 4wire brach circuits for range abd dryer, remove old GEC you have a the new one did not have access to inside house could not check subpanel or grds or bonds to water
ELE08-01298 Temporary Service5/19/20085/19/20085/19/2008 3:21:43 PMPPASS
david Phone #: ###-#### t/s u/g new ok
ELE08-01261 Permanent Service5/16/20085/19/20085/19/2008 1:50:08 PMPNR
Pump Service Inspection. Please call Eddy at ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Jeff Durham called
ELE08-01295 Permanent Service5/19/20085/19/20085/19/2008 1:07:38 PMPFAIL
Permanent pole for emissions test company Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called corr. posted250.24(A)(1) shall terminate GEC at neutral bus, 110.12(C) clean p/s of dirt and junk
ELE07-03859 Final5/19/20085/19/20085/19/2008 12:14:43 PMPFAIL
Must call Toby @ ###-#### 1/2 hour prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson
called still needs to remove GEC from raceways and boxes 250.64(E) & 250.92(A)(3)
ELE07-03859 Final5/16/20085/19/20085/19/2008 10:24:12 AMANH
Final Inspection. David Luke Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson no access talked to parks person
ELE08-00506 Electrical Rough-In5/19/20085/19/20085/19/2008 9:56:44 AMAPART
din rm grid ceiling ok
ELE08-00506 Final5/19/20085/19/20085/19/2008 9:14:48 AMACANC
ceiling inspection for cover in the dinning area Phone #: ###-#### Internet Inspection Request from: Spencer Mclean see added r/i
ELE08-01120 Permanent Service5/15/20085/19/20085/19/2008 9:12:48 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty p/s u/g new for meter
ELE08-00745 Electrical Rough-In5/16/20085/19/20085/19/2008 8:49:44 AMACANC
tom Phone #: ###-#### e grid coverd eleectrical contr , and pool contr responsible for grid
ELE08-01273 Electrical Rough-In5/16/20085/19/20085/19/2008 8:08:07 AMAPART
Greg, please call 30 minutes prior Phone #: ###-#### done by 370 friday