Inspections for the day of: Tuesday, May 19, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00394 Electrical Rough-In5/18/20095/19/20095/19/2009 4:16:25 PMPPASS
This is a rough ceiling inspection for Building A. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ceiling only ok to cover, met contractor
ESC08-00675 General Inspection5/19/20095/19/20095/19/2009 4:10:37 PMPPASS
looked ok
ESC09-00147 General Inspection5/19/20095/19/20095/19/2009 4:09:53 PMPPASS
looked ok
ESC08-00979 General Inspection5/19/20095/19/20095/19/2009 4:09:17 PMPPASS
looked ok
ELE09-00864 Electrical Rough-In5/19/20095/19/20095/19/2009 4:04:03 PMPPASS
Gene Phone #: ###-#### ric ok, no esc this project
ELE09-00836 Permanent Service5/19/20095/19/20095/19/2009 3:28:32 PMPCANC
This is to check the concrete encased electrode. If you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan called, wrong type request, see ri
ELE09-00836 Electrical Rough-In5/19/20095/19/20095/19/2009 2:43:22 PMPPASS
This is to check the concrete encased electrode. If you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan called, ok to pour concrete encased electrode
ELE08-01084 Electrical Rough-In5/19/20095/19/20095/19/2009 2:41:08 PMPPART
Xaiver- before 3 if possible- call prior to going Phone #: ###-#### ok to cover under floor cables only
ELE09-00801 Electrical Rough-In5/19/20095/19/20095/19/2009 1:37:01 PMPFAIL
eric - please call 1/2 hr prior Phone #: ###-#### met owner, gave corrections, NEC 210.52 (A) sjall add 2 receptacles for wall space, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, no esc this project
ELE09-00451 Electrical Rough-In5/18/20095/19/20095/19/2009 12:57:00 PMPPASS
brandon Phone #: ###-#### ok to cover u/g for extended panel relocation, no esc this project
ELE07-02374 Conference5/18/20095/19/20095/19/2009 10:15:22 AMADONE
andy - please call 1/2 hr prior Phone #: ###-#### reviewed service disconnect for garage or change panel to service rated panel, told owner building permit expired and that they to re-activate
ELE08-02776 Electrical Rough-In5/18/20095/19/20095/19/2009 9:49:20 AMAPASS
Jim- unit 533 Phone #: ###-#### ric ok, no esc this project
ELE09-00659 Final5/18/20095/19/20095/19/2009 9:14:52 AMAPASS
Rod Phone #: ###-#### ok to final, no esc this project
ELE09-00668 Electrical Rough-In5/18/20095/19/20095/19/2009 8:34:49 AMAFAIL
Ceiling inspection for cover Phone #: ###-#### Internet Inspection Request from: Celinda Winters called left message, left correction notice, NEC 210.62 Shall provide show room receptacles, 300.11(A) cables and raceways shall not be supported by ceiling grids, 110.16 shall provide arc flash warnings at service disconnect
ELE09-00668 Permanent Service5/18/20095/19/20095/19/2009 8:21:08 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s exst meter pak n ok , no esc this project