Inspections for the day of: Tuesday, May 19, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00086 INSP-Final Inspection5/19/20095/19/20095/20/2009 9:55:25 AMPPASS
Permit finaled.
FIR09-00126 INSP-Final Inspection5/19/20095/19/20095/19/2009 3:48:23 PMPPASS
Permit finaled
FIR05-00508 INSP-Final Inspection5/19/20095/19/20095/19/2009 3:35:57 PMPPASS
Permit finaled
BLD09-00105 FIRE-Final Inspection5/19/20095/19/20095/19/2009 3:29:41 PMPPASS
Life safety passed.
FIR08-00679 INSP-Alarm Testing5/19/20095/19/20095/19/2009 3:29:05 PMPFAIL
Resubmittals are required due to addressable notification devices installed instead of the standard devices. Also the smoke detectors model shown on the plans is not what has been installed. The initiating devices in the elevator shaft have been deleted per the state elevator inspector per brian with simplex. As-builts were on site but did not match the installation. The strobes on the second floor exterior balcony need modified to provide correct coverage. The manual pull station in the first floor lobby is mounted too high. The items tested that passed are phone lines, battery trouble, loss of a/c and the smoke detector over the facp. These signals were received at the central station. I request a manometer test of the duct smoke detectors on the first floor due to questionable positioning in the ducting.
FIR08-00675 INSP-Sprinkler Rough-in/Hydro5/19/20095/19/20095/19/2009 3:23:37 PMPCANC
Canceled due to the project related fire alarm system/permit not being complete. The backflow preventor has been certified. The fire alarm interconnections need to be tested/verified for final.
BLD09-00401 FIRE-Final Inspection5/19/20095/19/20095/19/2009 1:38:29 PMPPASS
life safety passed.
FIR08-00786 INSP-Alarm Testing5/18/20095/19/20095/19/2009 1:37:58 PMPCANC
Cancelled per conversation with Mark.
FIR09-00282 INSP-Sprinkler Rough-in5/19/20095/19/20095/19/2009 1:37:28 PMPPASS
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.
FIR09-00248 INSP-Sprinkler Rough-in5/19/20095/19/20095/19/2009 1:37:00 PMPPASS
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.
FIR09-00255 INSP-Sprinkler Rough-in5/18/20095/19/20095/19/2009 12:35:46 PMAPASS
The 2" underground supply piping is ok to cover. The contractor did not have the original approved plans, just copies, on site. I let him know those would be needed at the next inspection.
FIR06-00881 INSP-Final Inspection5/19/20095/19/20095/19/2009 10:48:18 AMPPASS
Permit finaled
FIR08-00720 FIR-Aging Inspection5/19/20095/19/20095/19/2009 9:25:42 AM NR
Work is in progress.
FIR09-00294 INSP-Final Inspection5/15/20095/19/20095/19/2009 9:07:41 AMAPASS
Permit finaled
FIR05-00750 INSP-Final Inspection5/15/20095/19/20095/19/2009 9:07:21 AMACANC
To be rescheduled per discussion with Guy.