Inspections for the day of: Wednesday, May 19, 2010.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00594 Permanent Service5/19/20105/19/20105/19/2010 3:44:48 PMPCANC
Inspection on outlet for sprinkler time clock. Inspection requested from web by: Emmet Bushman Phone #: ###-#### called contractor, told that he must get a separate permit, watch for service equipment and grounding
ELE10-01100 Conference5/19/20105/19/20105/19/2010 3:27:56 PMPDONE
Chad Phone #: ###-#### talked about service change, grounding and location
ELE10-01102 Electrical Rough-In5/19/20105/19/20105/19/2010 3:03:28 PMPPASS
Inspection requested from web by: kendall bender ric ok
ELE10-01096 Electrical Rough-In5/19/20105/19/20105/19/2010 2:19:11 PMPPASS
Need pool bonding and underground inspection
Thanks Inspection requested from web by: Lynn Cable Phone #: ###-#### u/g ok to cover, pool bonding only ok
ELE10-00666 Final5/19/20105/19/20105/19/2010 1:19:09 PMPPASS
Mike ###-#### - call 1/2 hr prior ok to final
ELE10-01075 Electrical Rough-In5/19/20105/19/20105/19/2010 12:33:10 PMPPASS
Contact: Dave Bradshaw Inspection requested from web by: Scott Campbell Phone #: ###-#### ric ok
ELE10-01097 Permanent Service5/19/20105/19/20105/19/2010 12:06:39 PMPPASS
Please inspect the Service Mast. THE CUSTOMER HAS BEEN WITHOUT POWER SINCE 5/18/10 AM after the storm. Inspection requested from web by: Clint Tate Phone #: ###-#### p/s o/h rec ok
ELE09-02356 Final5/18/20105/19/20105/19/2010 10:12:58 AMAPASS
Leslie-please call prior to inspection Phone #: ###-#### corrections made, ok to final
ELE10-01085 Rough-In Permanent Service5/18/20105/19/20105/19/2010 9:59:47 AMACANC
Larry Phone #: ###-#### see ri and final
ELE10-01085 Final5/19/20105/19/20105/19/2010 9:48:48 AMAPASS
Larry Phone #: ###-#### ok to final, signed card
ELE10-01085 Electrical Rough-In5/19/20105/19/20105/19/2010 9:45:53 AMAPASS
Larry Phone #: ###-#### ric ok
ELE10-00625 Rough-In Permanent Service5/18/20105/19/20105/19/2010 9:44:37 AMAFAIL
ROUGH-IN PERMANENT SERVICE READY IF QUESTIONS PLEASE CALL MIKE AT ###-####. Inspection requested from web by: Mike TenHulzen Phone #: ###-#### called contractor, told that NEC 250.24 shall connect gec to grounded concuctor at servive disconnect, shall provide meter, 310.4(B) parallel conductors shall be same length, check wireway under gear for correct size
ELE10-00146 Final5/18/20105/19/20105/19/2010 8:54:31 AMAPASS
mark - please call 1/2 hr prior so he can meet you there Phone #: ###-#### ok to final
ELE10-01086 Final5/18/20105/19/20105/19/2010 8:17:23 AMAPASS
please call patrick ###-#### one hour prior to going as you will need to be let in the building. Thank You Inspection requested from web by: Debby Ellis Phone #: ###-#### met contractor, ok to final
ELE09-00190 DOC - Permit Expired5/19/20105/19/20105/19/2010 6:34:45 AMAPASS
no activity, ok to doc expire
ELE06-01646 ELE-Aging Inspection5/19/20105/19/20105/19/2010 6:29:36 AM DONE
see doc expire
ELE06-01646 DOC - Permit Expired5/19/20105/19/20105/19/2010 6:29:24 AMAPASS
no activity, ok to doc expire
ELE06-01603 ELE-Aging Inspection5/19/20105/19/20105/19/2010 6:28:10 AM DONE
see doc expire
ELE06-01603 DOC - Permit Expired5/19/20105/19/20105/19/2010 6:27:57 AMAPASS
no activity, ok to doc expire