Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00952 Final5/19/20145/19/20145/19/2014 3:38:41 PMPFAIL
rosalie Phone #: ###-#### Home owner has not called for conference as reqwested on form PDS 424-B.
I requested a conference to discuss issues with service and some dangerous over head conductors to out building. Overhead conductors are at 6'9", 7'3" and 8" to out building. shall be removed due to hieght and illegal terminations. Wires shall be properly terminated exiting house.
BCC 4-05-32 Code violation not to be retained.
Owner's son not available to meet so sent a friend so I could inform of issues.
110.26 work platform needs 36" depth from front of service.
ELE14-01163 Electrical Rough-In5/19/20145/19/20145/19/2014 2:52:33 PMPPASS
Greg Critchfield is contact ###-####, service wiring. thank you Phone #: ###-#### >> Inspection requested via web by Debby Pierce Conduits for new elevator equiptment rough in ok
ELE12-00802 Final5/19/20145/19/20145/19/2014 2:27:29 PMPPASS
Greg Critchfield is contact, ###-####. thank you Phone #: ###-#### >> Inspection requested via web by Debby Pierce This permit covers installation of new service and prep work to provide conduits and junction points for quick disconnect of old gear and quick reconnect to new. Future permit will cover the change over from old gear to new gear. Conference in 2012 electrician stated city gave permission to feed fire pump from normal and emergency power in rigid conduit with out fire barrier. For work done to this point Final ok
ELE14-00791 Electrical Rough-In5/19/20145/19/20145/19/2014 12:59:54 PMPPASS
This is a grid inspection. Contact on the job is Nate Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery 1 st floor corridor, 2nd floor 2 offices, library, engeneering grid rough in ok cover
ELE14-01134 Final5/16/20145/19/20145/19/2014 9:58:25 AMAPASS
Troy Phone #: ###-#### Final ok
ELE14-00158 Electrical Rough-In5/16/20145/19/20145/19/2014 9:11:47 AMACANC
Service Inspection, not sure if i clicked the right "Inspection Type". Geoff Hannaford is the contact on this project, ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Pierce Needed P/S inspection
ELE14-00158 Permanent Service5/19/20145/19/20145/19/2014 9:11:31 AMPPASS
Service Inspection, not sure if i clicked the right "Inspection Type". Geoff Hannaford is the contact on this project, ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Pierce p/s o/h n ok