Inspections for the day of: Monday, May 19, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00308 INSP-Sprinkler Rough-in5/16/20145/19/20145/19/2014 4:06:42 PMPPART
Inspection for modifications at the 1st and 2nd floor existing adjacent office and breakroom areas. This work to be shown on revised drawings per discussion.
BLD14-00150 FIRE-Final Inspection5/19/20145/19/20145/19/2014 4:01:35 PMPPASS
Derek-please 1/2 hr prior Phone #: ###-####
FIR14-00124 INSP-Final Inspection5/19/20145/19/20145/19/2014 3:53:18 PMPNR
BLD13-03384 FIRE-Final Inspection5/16/20145/19/20145/19/2014 12:25:09 PMAPEND
Pending plan modification and permit related FIR trade work.
FIR14-00229 INSP-Final Inspection5/18/20145/19/20145/19/2014 12:23:38 PMAPART
Final pending water supply for verification of waterflow switch function. Remainder of fire alarm work tested satisfactory including tampers, MP, FACP, RA, trouble conditions, offsite monitoring, etc. Noted a heat detector at the panel has been installed in place of a SD due to adjacent equipment.
BLD14-00725 FIRE-Final Inspection5/16/20145/19/20145/19/2014 10:48:07 AMAFAIL
Need to repair one EM light, secure open light fixture wiring at the storage room, repair exit sign at the west exit. Hood suppression system modifications are in process and will require a permit and inspection prior to final. Project finishes underway.
FIR14-00251 INSP-Final Inspection5/16/20145/19/20145/19/2014 10:16:19 AMAPART
Overhead fire sprinkler system modifications and additions at the first floor and mezzanine levels passed rough-in- Okayed for cover.