Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF14-00007 INSP-Final5/18/20155/19/20155/20/2015 1:02:36 PMAPASS
Life safety passed
BLD15-00081 FIRE-Final Inspection5/19/20155/19/20155/19/2015 3:54:51 PMPPASS
life safety passed
FIR15-00002 INSP-Sprinkler Rough-in5/18/20155/19/20155/19/2015 3:40:50 PMPCANC
Overbooked. Rescheduled for tomorrow morning
FIR15-00064 INSP-Alarm Testing5/18/20155/19/20155/19/2015 3:36:53 PMADONE
Todays inspection verified the FACP and the NAC panel. Also verified tamper switches as marked on the city approved plans. Also verifed placement and function of the first floor NAC circuits/devices. I noted several overspaced strobes as marked on the plans. I spoke to the general contractor about duct smoke detectors (he is waiting on an RFI)
FIR15-00056 INSP-Final Inspection5/14/20155/19/20155/19/2015 12:20:51 PMAFAIL
Lack of strobe coverage in front of pharmacy, discussed solution with contractor to correct said issue, will need to provide as build drawings.
FIR15-00254 INSP-Final Inspection5/18/20155/19/20155/19/2015 10:32:16 AMPFAIL
1. Monitoring service not set up correctly.
2. All devices will need to be retested.
3. Need to provide knox box.
4. Provide document cabinet.
FIR14-00910 INSP-Final Inspection5/18/20155/19/20155/19/2015 10:29:26 AMAFAIL
1.No pressure relief valve installed.
2. Backflow assembly neededs to be tested by certified backflow tester.
3. Forward flush needs to be performed.
4. No ball drip on FDC.
5. Fire alarm needs to be retested.
FIR15-00335 INSP-Sprinkler Rough-in5/19/20155/19/20155/19/2015 10:24:09 AMPCANC
This is an underground to cover inspection with concrete scheduled to arrive at 1pm. Bryan is the contact. Thanks! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR15-00264 INSP-Alarm Testing5/18/20155/19/20155/19/2015 10:22:56 AMAPASS
Permit Finaled
FIR11-00314 INSP-Final Inspection5/19/20155/19/20155/19/2015 8:52:08 AMAPASS
Permit Finaled
FIR15-00049 INSP-Final Inspection5/19/20155/19/20155/19/2015 8:50:26 AMAPASS
Permit Finaled
BLD15-00749 FIRE-Final Inspection5/18/20155/19/20155/19/2015 7:11:03 AMAPASS
Life safety passed
FIR14-00069 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/18/2015 1:38:37 PMPCANC
Rough in Hydro UG
Please call Leroy 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
FIR14-00683 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/18/2015 1:38:27 PMPCANC
Rough-in Hydro Wet and Dry
Please call Leroy 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt