Inspections for the day of: Tuesday, May 19, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00036 INSP-Final Inspection5/18/20155/19/20155/20/2015 11:32:17 AMPPASS
Fire sprinkler system final - PASSED. All alarm connections tested OK. ROC and as-built plans provided.
FIR14-00921 INSP-Final Inspection5/18/20155/19/20155/20/2015 11:30:31 AMPPASS

Fire monitoring system final inspection - PASSED. All systems/components tested OK
BLD13-00181 FIRE-Conference5/18/20155/19/20155/19/2015 1:43:10 PMADONE
Meeting to discuss upcoming fire alarm testing and subsequent occupancy (TCO) of wings A thru D.
FIR14-00069 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/19/2015 1:40:14 PMAPASS
Hydrotest of FSUG system - from city check valve to BFP. No loss of pressure noted for 2 hours. System has been flushed at previous inspection.
FIR14-00683 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/19/2015 1:37:46 PMAPASS
Hydrotest of wet and dry pipe systems - no leaks noted. Pressure held for 2 hours.
FIR14-00531 INSP-Sprinkler Rough-in/Hydro5/19/20155/19/20155/19/2015 12:07:14 PMPPASS
Rough-in of fitness room dry system, elevator loobies for elevator #1 (floors 2 thru 5), and 3rd floor pod soffits for Tower 3.
No discrpancies noted.
FIR14-00531 INSP-Sprinkler Rough-in5/18/20155/19/20155/19/2015 11:58:27 AMACANC
Rough-in inspection of fitness room dry system. Also elevator lobbies for elevator #1 (floors 2 thru 5) and 3rd fllor pod soffits located in tower 3.
No discrepancies noted.
FIR13-00725 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/19/2015 11:55:39 AMAPASS
Hydrotest of Helix thrid floor dry system, which includes helix ramp, multimedia room and inspiration room, with mechanical room above. Found one (1) obstructed A/S in lobby of multimedia room that will have to be extended below surface mounted light. No other discrepncies noted.
FIR14-00252 INSP-Sprinkler Rough-in/Hydro5/18/20155/19/20155/19/2015 11:51:21 AMACANC

Found leak in the kitchen system - inspection cancelled