FIR15-00036
| INSP-Final Inspection | 5/18/2015 | 5/19/2015 | 5/20/2015 11:32:17 AM | P | PASS |
|
|
Fire sprinkler system final - PASSED. All alarm connections tested OK. ROC and as-built plans provided.
|
FIR14-00921
| INSP-Final Inspection | 5/18/2015 | 5/19/2015 | 5/20/2015 11:30:31 AM | P | PASS |
|
|
Fire monitoring system final inspection - PASSED. All systems/components tested OK
|
BLD13-00181
| FIRE-Conference | 5/18/2015 | 5/19/2015 | 5/19/2015 1:43:10 PM | A | DONE |
|
|
Meeting to discuss upcoming fire alarm testing and subsequent occupancy (TCO) of wings A thru D.
|
FIR14-00069
| INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 1:40:14 PM | A | PASS |
|
|
Hydrotest of FSUG system - from city check valve to BFP. No loss of pressure noted for 2 hours. System has been flushed at previous inspection.
|
FIR14-00683
| INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 1:37:46 PM | A | PASS |
|
|
Hydrotest of wet and dry pipe systems - no leaks noted. Pressure held for 2 hours.
|
FIR14-00531
| INSP-Sprinkler Rough-in/Hydro | 5/19/2015 | 5/19/2015 | 5/19/2015 12:07:14 PM | P | PASS |
|
|
Rough-in of fitness room dry system, elevator loobies for elevator #1 (floors 2 thru 5), and 3rd floor pod soffits for Tower 3. No discrpancies noted.
|
FIR14-00531
| INSP-Sprinkler Rough-in | 5/18/2015 | 5/19/2015 | 5/19/2015 11:58:27 AM | A | CANC |
|
|
Rough-in inspection of fitness room dry system. Also elevator lobbies for elevator #1 (floors 2 thru 5) and 3rd fllor pod soffits located in tower 3. No discrepancies noted.
|
FIR13-00725
| INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 11:55:39 AM | A | PASS |
|
|
Hydrotest of Helix thrid floor dry system, which includes helix ramp, multimedia room and inspiration room, with mechanical room above. Found one (1) obstructed A/S in lobby of multimedia room that will have to be extended below surface mounted light. No other discrepncies noted.
|
FIR14-00252
| INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 11:51:21 AM | A | CANC |
|
|
Found leak in the kitchen system - inspection cancelled
|