Inspections for the day of: Thursday, May 19, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00557 Electrical Rough-In5/18/20165/19/20165/19/2016 3:09:09 PMPPASS
Contact is Ben MacDonagh Phone #: ###-#### Inspection requested via web by Scott Campbell rough-in ok cover consultation room walls
ELE16-01553 Electrical Rough-In5/18/20165/19/20165/19/2016 11:25:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams exterior corrections not completed, interior ceiling and walls ok to cover
ELE16-00798 Final5/18/20165/19/20165/19/2016 10:40:19 AMAPASS
5050 + enter Phone #: ###-#### Inspection requested via web by HZ ZAHIC final ok
ELE16-01327 Final5/18/20165/19/20165/19/2016 10:21:40 AMAFAIL
Phone #: ###-#### Inspection requested via web by Tyler Bowen NEC 600.6 Disconnect for LED lettering requires to be within sight or breaker lock-out. NEC 210.8(B)(1) Bathroom receptacles requires GFCI protection NEC 422.52 Electric drinking fountain requires GFCI protection, Faulty GFCI breaker?
ELE16-01128 Electrical Rough-In5/18/20165/19/20165/19/2016 10:15:46 AMAPASS
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listed LED lettering rough-in ok
ELE16-01582 Electrical Rough-In5/18/20165/19/20165/19/2016 9:09:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot rough-in ok cover kitchen/dinning area only