BLD16-00921
| FIRE-Final Inspection | 5/18/2016 | 5/19/2016 | 5/20/2016 3:24:48 PM | A | PART |
|
|
No fire sprinklers, no fire alarm panel, fire extinguishers are in place with current inspection tags, exit signs are in place and operational, in duct detectors are stand alone and duct detectors have been tested/passed. There are multiple doors throughout the space that have round type door hardware installed, informed general contractor that the round type door hardware may need to be changed to paddle type door hardware based on final building inspector requirements. Exterior exit doors have a maglock assemblies installed on door frame with push button exit only, doors with maglocks need to have sensors as well as push button operation installed on egress side for door release. Life fire safety inspection is complete with exception to maglock release, life fire safety can be finaled once maglock operation has been tested and inspected.
|
FIR16-00295
| INSP-Sprinkler Rough-in | 5/19/2016 | 5/19/2016 | 5/19/2016 3:55:08 PM | P | PASS |
|
|
Rough to cover inspection complete for underground piping, underground main line approved for cover.
|
FIR15-00709
| INSP-Sprinkler Rough-in | 5/19/2016 | 5/19/2016 | 5/19/2016 1:58:11 PM | P | PART |
|
|
Rough to cover inspection complete for level 3 corridor soffits, level 3 corridor soffits approved for cover.
|
BLD15-02076
| FIRE-Final Inspection | 5/18/2016 | 5/19/2016 | 5/19/2016 10:07:20 AM | A | PASS |
|
|
Fire sprinkler inspection complete (FIR15-00572), fire alarm inspection complete (FIR15-00475), final life fire safety inspection passed/complete.
|
FIR15-00572
| INSP-Final Inspection | 5/18/2016 | 5/19/2016 | 5/19/2016 10:05:09 AM | A | PASS |
|
|
Final fire sprinkler inpsection passed/complete.
|
FIR16-00288
| INSP-Sprinkler Rough-in/Hydro | 5/18/2016 | 5/19/2016 | 5/19/2016 12:00:00 AM | A | CANC |
|
|