Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01510 Temporary Service5/18/20175/19/20175/19/2017 11:23:44 AMAPASS
Questions ask for Ben Phone #: ###-#### Inspection requested via web by Ben Grundhauser
t/s u/g n ok
ELE17-01509 Rough-In Permanent Service5/18/20175/19/20175/19/2017 11:23:06 AMAFAIL
Questions ask for Ben Phone #: ###-#### Inspection requested via web by Ben Grundhauser
300.4- NM and other cables shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface. Above panels in garage. to front recept. out entry.
334.30- Flat cables shall not be stapled on edge.
210.52(B)- If counter space is present at time of final receptacle spacing for kitchen ounter top areas required.
* WUI zone A construction for cans in outer soffits.