Inspections for the day of: Friday, May 19, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01339 Permanent Service5/19/20175/19/20175/19/2017 3:19:38 PMPPASS
There will be guys there working. If you have any questions please call Ryan ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan p/s u/g n ok
ELE10-01996 ELE-Aging Inspection5/19/20175/19/20175/19/2017 12:52:25 PM DONE
Stopped by project. Was able to inspect
ELE10-01996 Final5/19/20175/19/20175/19/2017 12:51:49 PMPPASS
Inspected project. No violations found Final ok
ELE17-00717 Final5/19/20175/19/20175/19/2017 12:30:58 PMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk corrections made final ok
ELE17-01524 Temporary Service5/19/20175/19/20175/19/2017 12:21:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Jay Hutchison t/s u/g n ok
ELE17-01515 Rough-In Permanent Service5/18/20175/19/20175/19/2017 10:55:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
ELE17-00717 Final5/18/20175/19/20175/19/2017 9:43:39 AMAFAIL
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk 314.20 Boxes set back more than 1/4in shall have extension ring. (Up bath 2 gang) 210.8 GFCI shall be readily accessible. (Garage opener temp still installed)
ELE17-01480 Temporary Service5/18/20175/19/20175/19/2017 9:00:04 AMAFAIL
Travis is contact Phone #: ###-#### Inspection requested via web by Stacie Tasker Sch80 PVC shall be used where exposed to physical damage. (Feder coduit to transformer) In use cover missing on temp recep.