MEC20-01626
| Final | 5/13/2020 | 5/19/2020 | 5/19/2020 3:38:24 PM | P | PASS |
|
|
Call or text Christine in route to inspection ###-####--equipment is in mechanical room outside house Phone #: ###-#### Inspection requested via web by Justin Osterhout- a/c coil co locking caps ok
|
MEC20-00277
| Rough-in | 5/19/2020 | 5/19/2020 | 5/19/2020 3:13:17 PM | P | PART |
|
|
for soffit inspection please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN-R/I 4th floor 4 units ok to cover- seal ok on exhaust supply and dryer ducts ok
|
MEC20-01943
| Final | 5/18/2020 | 5/19/2020 | 5/19/2020 2:49:10 PM | P | PASS |
|
|
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok
|
MEC20-01130
| Final | 5/19/2020 | 5/19/2020 | 5/19/2020 2:12:12 PM | P | FAIL |
|
|
GARAGE CODE: 7445 Phone #: ###-#### Inspection requested via web by Kristy Watson- primary condensate off coil needs 1/4" per foot slope to drain and supported/secure with hanger-
|
MEC20-01292
| Final | 5/19/2020 | 5/19/2020 | 5/19/2020 1:51:02 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tim Petsche- dryer ducting needs 6" clearance to combustibles at roof 2012 IMC 504.7- dryer installations instruction do not address clearances- GC is aware of issues- need roof access at final- still need engineer approval for ducting installed that different thsn approved prints-
|
MEC20-01690
| Final | 5/19/2020 | 5/19/2020 | 5/19/2020 12:51:57 PM | P | PASS |
|
|
final ok- corrections made
|
MEC20-01890
| Final | 5/18/2020 | 5/19/2020 | 5/19/2020 12:51:17 PM | P | PASS |
|
|
Please call our installer Devin on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- final ok- framing omitted around b vent not doing
|
MEC20-01958
| Pressure Test | 5/19/2020 | 5/19/2020 | 5/19/2020 11:40:21 AM | P | CANC |
|
|
Please contact Jasper with any questions Phone #: ###-#### Inspection requested via web by Ted Dumont Inc.- per phone call with Jasper will reschedule-
|
MEC20-01545
| Rough-in | 5/18/2020 | 5/19/2020 | 5/19/2020 10:16:59 AM | A | PASS |
|
|
Ceiling inspection at the grid. Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- flex registers and insulation ok- ok for ceiling tiles
|
MEC20-01722
| Final | 5/18/2020 | 5/19/2020 | 5/19/2020 9:42:10 AM | A | NR |
|
|
Screened- Joe Phone #: ###-####- need to pressure test gas line to 20 psi on 30psi gauge max- went over with homeowner- reschedule when ready
|
MEC20-01902
| Final | 5/18/2020 | 5/19/2020 | 5/19/2020 8:35:02 AM | A | PASS |
|
|
Please inspect as early as possible. Dora Ferrer ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co locking caps ok
|
MEC19-03433
| Mec-Aging Inspection | 5/19/2020 | 5/19/2020 | 5/19/2020 8:17:58 AM | | CANC |
|
|
permit expired
|
MEC19-03433
| DOC - Permit Expired | 5/19/2020 | 5/19/2020 | 5/19/2020 8:17:45 AM | A | PASS |
|
|
no calls- permit expired
|
MEC19-03452
| Mec-Aging Inspection | 5/19/2020 | 5/19/2020 | 5/19/2020 8:17:07 AM | | CANC |
|
|
permit expired
|
MEC19-03452
| DOC - Permit Expired | 5/19/2020 | 5/19/2020 | 5/19/2020 8:16:55 AM | A | PASS |
|
|
no calls- permit expired
|