BLD00-03697
| FIRE-Final Inspection | 5/1/2001 | 5/2/2001 | 5/2/2001 12:00:00 AM | A | FAIL |
|
|
###-#### exit signs; fire extinguishers; alarm and fire sprinkler signs; door hardware 5/2/2001 9:56:48 AM
|
FIR01-00066
| INSP-Sprinkler Rough-in/Hydro | 5/1/2001 | 5/2/2001 | 5/2/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 05/01/2001 at 14:24:52. Contact: ###-####. need FDC location adjusted to maintain 3 foot clearance; above and underground hydro okay 5/2/2001 10:20:56 AM
|
BLD01-00428
| FIRE-Sprinkler Rough-in | 5/2/2001 | 5/2/2001 | 5/2/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 5/2/2001 9:53:43 AM
|
BLD01-00393
| FIRE-Final Inspection | 5/1/2001 | 5/2/2001 | 5/2/2001 12:00:00 AM | P | FAIL |
|
|
Terry ###-#### need alarm plans and to test alarms; sprinkler escutcheons 5/2/2001 3:26:02 PM
|
FIR01-00133
| INSP-Final Inspection | 5/1/2001 | 5/2/2001 | 5/2/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 05/01/2001 at 14:05:05. Contact: ###-####. need to instal batteries per plans; exposed conduit with openings; define zones; comm fault when dialing 5/2/2001 3:27:02 PM
|