Inspections for the day of: Thursday, May 2, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00587 INSP-Final Inspection4/29/20025/2/20025/2/2002 12:00:00 AMAFAIL
Fire sprinkler riser devices have been tested along with one duct detector above the panel room. All other detectors and items in panel need to be tested 5/3/2002 8:25:22 AM
BLD01-00308 FIRE-Final Inspection5/1/20025/2/20025/2/2002 12:00:00 AMAFAIL
change door hardware to ADA approved type (lever - same for locks if equiped), remove thumbturns on exit doors, place sticker on main door if it becomes keyed, provide fire extinguisher with current inspection tag, provide exit sign in basement per approved plans 5/2/2002 4:29:35 PM
BLD01-00617 FIRE-Final Inspection5/1/20025/2/20025/2/2002 12:00:00 AMACANC
duplicate inspection 5/2/2002 2:04:38 PM
BLD01-00617 FIRE-Final Inspection5/1/20025/2/20025/2/2002 12:00:00 AMPFAIL
elevator recall did not work, change door hardware to ADA approved type, remove thumbturn and put up sticker on main exit, provide fire extinguisher, relocate 2nd floor smoke detector to deck, verify need for "knox box". Approved plan notes are missing. Notified Val that there may be other items on the notes that will need addressing 5/2/2002 3:30:18 PM