Inspections for the day of: Friday, May 2, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00078 INSP-Final Inspection4/30/20035/2/20035/2/2003 12:00:00 AMAFAIL
###-####. The sprinkler heads as installed do not match the fire sprinkler plans. The max. head spacing is for 130 sq. ft. and this is exceeded in many locations. Upright sprinkler heads need to be added. 5/2/2003 9:41:11 AM
BLD01-02557 FIRE-Final Inspection5/1/20035/2/20035/2/2003 12:00:00 AMAFAIL
###-####. Test duct smoke detectors, provide ADA approved hardware on all doors including the sliding glass doors, the pocket doors and the exterior doors that have the thumbturns on them. 5/2/2003 12:23:19 PM
BLD03-00483 FIRE-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMAFAIL
Inspection was for a conference. No sprinkler work has been done and the duct smoke detector needs tested.
FIR00-00007 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Permit finaled under the building permit
FIR00-00529 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Permit finaled under the building permit
FIR00-00083 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Inspection was finaled by 406. I am DOC finaling
FIR00-00096 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Inspection passed by 406. I'm DOC finaling
FIR00-00511 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Sprinklers passed by 406 on 12/6/2001 under the building permit
FIR00-00315 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Sprinklers passed by 406 on 12/6/2001 under the building permit
FIR00-00216 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
Sprinklers passed by 406 on 12/6/2001 under the building permit
FIR02-00380 INSP-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
BLD02-00752 FIRE-Final Inspection5/2/20035/2/20035/2/2003 12:00:00 AMPPASS
fire life safety and fire alarm finaled
FIR02-00380 INSP-Final Inspection4/30/20035/2/20035/2/2003 12:00:00 AMPDONE
Inspection already finaled 5/2/2003 3:34:33 PM