Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01050 Electrical Rough-In4/29/20055/2/20055/2/2005 12:00:00 AMAPASS
potting compound around pool///kevin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa potting ok 5/2/2005 9:16:55 AM
ELE04-03672 Final4/29/20055/2/20055/2/2005 12:00:00 AMANR
STEVE ; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy need plans changed to finish core 5/2/2005 10:38:06 AM
ELE05-01062 Final4/29/20055/2/20055/2/2005 12:00:00 AMAPART
please call Ed Schallock with any questions; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 1/2 done, with change over ok 5/2/2005 9:15:10 AM
ELE05-01464 Electrical Rough-In4/29/20055/2/20055/2/2005 12:00:00 AMAPASS
verna; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ric ok, ok to cover gec, but need to see after poured,before backfill 5/2/2005 9:54:11 AM
ELE05-01326 Final4/28/20055/2/20055/2/2005 12:00:00 AMAPASS
rick ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final 5/2/2005 9:15:42 AM
ELE05-01481 Electrical Rough-In4/29/20055/2/20055/2/2005 12:00:00 AMPFAIL
###-#### danette or leon called contr, left message, left corr notice,250.64(D) gnd elec condr shall tap outside of enclosure, 312.5 gnd elec cndr shall be protected against abrasion,300.4(A)(1) & (D) nail plates and 1 1/4" from edge of framing members shall be provided, 210.8(A) counter top recpts shall be gfci (peninsula), 210.52(B)(2) small applisnce branch ckts shall have no other outlets,BCC All make-up shall be done,Job ID shall be posted,Approved set of plans shall be on job. 5/2/2005 4:27:36 PM
ELE05-01382 Rough-In Permanent Service5/2/20055/2/20055/2/2005 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn ric ok , p/s u/g n ok 5/2/2005 1:01:52 PM
ELE05-01502 Rough-In Permanent Service5/2/20055/2/20055/2/2005 12:00:00 AMPPASS
clyde ###-#### ric ok , p/s u/g n ok 5/2/2005 12:20:18 PM
ELE04-02171 Final5/2/20055/2/20055/2/2005 12:00:00 AMPPASS
ellen; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections done, ok to final 5/2/2005 2:46:00 PM
ELE05-01507 Final5/2/20055/2/20055/2/2005 12:00:00 AMPPASS
replaced damaged meter base -- ###-#### dan p/s u/g exst ok 5/2/2005 2:57:10 PM