ELE06-00899
| Temporary Service | 5/1/2006 | 5/2/2006 | 5/3/2006 2:02:13 PM | A | PASS |
|
|
Olga; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called cont, left survey, nec 312.5 all conductors entering enclosures shall have abrasion protection, 406.4 recept shall be securely fastened in place t/s u/g n ok
|
ELE06-00898
| Temporary Service | 5/1/2006 | 5/2/2006 | 5/3/2006 2:01:26 PM | A | PASS |
|
|
Olga; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left survey, nec 312.5 all conductors entering enclosures shall have abrasion protection t/s u/g n ok
|
ELE06-01438
| Electrical Rough-In | 5/2/2006 | 5/2/2006 | 5/2/2006 4:33:08 PM | P | PART |
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover west end of basement and sanctuary area, talked to contr about fix 1 piece of damaged mc cable
|
ELE06-00116
| Permanent Service | 5/2/2006 | 5/2/2006 | 5/2/2006 4:01:20 PM | P | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked w/contr, left corr notice, nec 314.28 (A)(2) pull and junction box shall be sized for angle pulls- not less than 16" opposite wall of 2" conduits
|
ELE06-01374
| Final | 5/2/2006 | 5/2/2006 | 5/2/2006 3:35:27 PM | P | PASS |
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-01374
| Permanent Service | 5/2/2006 | 5/2/2006 | 5/2/2006 3:34:43 PM | P | PASS |
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s exst meter pak n ok
|
ELE06-01516
| Final | 5/2/2006 | 5/2/2006 | 5/2/2006 2:43:48 PM | P | FAIL |
|
|
Brent Lee; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection,362.30 ent shall be strapped within 3' of box and every 3',BCC address shall be posted, job id sticker shall be posted, u/g shall be inspected before cover
|
ELE06-00117
| Electrical Rough-In | 5/2/2006 | 5/2/2006 | 5/2/2006 2:16:50 PM | P | PART |
|
|
mike - Note: wall; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls west end and north soffit ok to cover only
|
ELE06-01521
| Temporary Service | 5/2/2006 | 5/2/2006 | 5/2/2006 1:02:25 PM | P | PASS |
|
|
###-#### - spencer t/s u/g n ok
|
ELE06-00461
| Electrical Rough-In | 5/2/2006 | 5/2/2006 | 5/2/2006 12:07:17 PM | P | PASS |
|
|
marshal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met owner told to use 15a bkrs on 14awg wire, add 1 recpt on computer wall, ric ok
|
ELE06-01506
| Temporary Service | 5/1/2006 | 5/2/2006 | 5/2/2006 10:38:16 AM | A | PASS |
|
|
verna ###-#### t/s u/g n ok
|
ELE06-00113
| Electrical Rough-In | 5/1/2006 | 5/2/2006 | 5/2/2006 10:22:08 AM | A | PART |
|
|
contact: Greg Pack ceiling rough-in on 7th floor; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ri ok 7th floor ceiling anop
|
ELE05-04167
| Final | 5/1/2006 | 5/2/2006 | 5/2/2006 8:48:43 AM | A | PASS |
|
|
Final - homeowner - Bruce- will be there in the morning. Scheduled by Heather Packer w/ Doherty ; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to final
|