FIR06-00256
| INSP-Sprinkler Rough-in | 5/2/2006 | 5/2/2006 | 5/3/2006 8:07:34 AM | P | NR |
|
|
Hydrostatic test not ready for inspection per contractor, to be rescheduled.
|
BLD05-02358
| FIRE-Final Inspection | 5/2/2006 | 5/2/2006 | 5/3/2006 8:06:05 AM | P | NR |
|
|
The project related fire sprinkler permit must be finaled before life safety final approval.
|
BLD05-00087
| FIRE-Conference | 5/2/2006 | 5/2/2006 | 5/2/2006 3:09:15 PM | P | DONE |
|
|
On site confrence to discuss emergency lighting requirements for the path of egress as indicated on approved plans.
|
FIR05-00600
| INSP-Sprinkler Rough-in | 5/2/2006 | 5/2/2006 | 5/2/2006 2:59:33 PM | P | PART |
|
|
UG hydrostatic test passed inspection.
|
MIS06-00081
| FIR-Final | 4/25/2006 | 5/2/2006 | 5/2/2006 12:57:06 PM | P | FAIL |
|
|
Need to provide building address, provide fire extinguisher with current certification tag, cover open electrical boxes, provide approved door hardware at the main entry/exit door, remove or provide correct hardware at the remaining doors, partitions and gates have not been installed at this time as shown on plan.
|
FIR05-00398
| INSP-Sprinkler Rough-in | 5/1/2006 | 5/2/2006 | 5/2/2006 11:27:47 AM | P | PASS |
|
|
The remainder of overhead work for this permit is good for cover, project is ready for final when all ceiling tile is installed.
|
FIR06-00140
| INSP-Sprinkler Rough-in | 5/1/2006 | 5/2/2006 | 5/2/2006 11:25:48 AM | P | PART |
|
|
Overhead rough-in is good for cover at the drop ceiling areas as marked on approved plans, two rooms at the NE corner are not complete or inspected at this time.
|
FIR05-00846
| INSP-Final Inspection | 5/1/2006 | 5/2/2006 | 5/2/2006 11:19:05 AM | A | PASS |
|
|
Fire sprinkler work is satisfactory, inspection passed, permit finaled.
|
BLD04-03034
| FIRE-Final Inspection | 5/1/2006 | 5/2/2006 | 5/2/2006 11:17:52 AM | A | DONE |
|
|
Duplicate inspection request already completed.
|
BLD04-03034
| FIRE-Final Inspection | 5/1/2006 | 5/2/2006 | 5/2/2006 9:46:03 AM | A | FAIL |
|
|
The project related fire sprinkler permit must be finaled prior to life safety approval, some items noted on walk through include exit sign at the SW door needs repaired, manual flush bolts on the inactive leaf at the north exit are not allowed, need to test emergency lights, provide lever hardware at the paint room door, provide approved building plans and review notes at the next inspection, not all items reviewed at this time.
|
FIR06-00296
| INSP-Sprinkler Rough-in | 5/1/2006 | 5/2/2006 | 5/1/2006 12:00:00 AM | P | CANC |
|
|
###-#### Mike\\per Mary can not have insp.
|