FIR06-00857
| FIR-Aging Inspection | 5/2/2007 | 5/2/2007 | 5/4/2007 1:53:18 PM | | DONE |
|
|
wip
|
FIR06-00540
| INSP-Sprinkler Rough-in | 4/25/2007 | 5/2/2007 | 5/2/2007 5:08:09 PM | P | NR |
|
|
Fire Pump Test (Forrest) and for Info Sam Per a conversation with Sam this morning we will do a pump run complete with test header flows,bypass flows,emergency power transfer. Phone #: ###-#### Internet Inspection Request from: Lynn Beus ............ Per conversation with the foreman on site, pump testing pending replacement of one component at the discharge side and scheduling with the pump mfr. rep to be present during testing.
|
FIR07-00174
| INSP-Supply line flush | 5/1/2007 | 5/2/2007 | 5/2/2007 5:00:34 PM | P | PART |
|
|
UG supply line flush completed.
|
FIR07-00240
| INSP-Sprinkler Rough-in/Hydro | 5/2/2007 | 5/2/2007 | 5/2/2007 4:59:40 PM | P | PART |
|
|
Begin air test 2:35 pm @ 52psi. as marked on guage.
|
BLD05-01077
| FIRE-Final Inspection | 4/30/2007 | 5/2/2007 | 5/2/2007 3:07:11 PM | A | DEFR |
|
|
Inspection rescheduled per conversation with building engineer.
|
FIR07-00312
| INSP-Sprinkler Rough-in | 5/1/2007 | 5/2/2007 | 5/2/2007 2:32:24 PM | A | PART |
|
|
OH install is satisfactory, noted approval for cover pending inspection for cold cavity protection (tenting) as discussed with contractor.
|
BLD06-01131
| FIRE-Final Inspection | 5/1/2007 | 5/2/2007 | 5/2/2007 1:06:14 PM | A | PASS |
|
|
Final fire life safety inspection passed, noted corrections complete.
|
FIR07-00204
| INSP-Sprinkler Rough-in | 5/1/2007 | 5/2/2007 | 5/2/2007 12:50:19 PM | A | PART |
|
|
Overhead rough-in at the 1st and 2nd floor elevator lobby and restroom hard lids are good for cover as red lined on approved plans.
|
FIR07-00240
| INSP-Sprinkler Rough-in | 5/1/2007 | 5/2/2007 | 5/2/2007 12:12:00 PM | A | PART |
|
|
OH installation is acceptable, hydrostatic test of the preaction system completed, noted changes at preaction riser including drain termination point, different PRV than what is submitted, riser trim has been modified to include a potter ps40 in lieu of the mfg. supplied pressure switch.
|
FIR07-00255
| INSP-Final Inspection | 5/2/2007 | 5/2/2007 | 5/2/2007 9:24:17 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-01077
| FIRE-Final Inspection | 4/30/2007 | 5/2/2007 | 4/30/2007 10:57:47 AM | A | CANC |
|
|
jim - fire life safety ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Andrea Whiteman
|