Inspections for the day of: Friday, May 2, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00606 INSP-Sprinkler Rough-in/Hydro5/1/20085/2/20085/5/2008 9:28:34 AMPPART
OH hydrostatic test passed for system #2 only.
FIR07-00505 INSP-Sprinkler Rough-in/Hydro5/1/20085/2/20085/2/2008 3:49:48 PMPPART
UG fire supply line and remote FDC piping passed hydrostatic testing.
BLD08-00706 FIRE-Final Inspection5/1/20085/2/20085/2/2008 3:47:52 PMAPASS
Correction items are finished, occupant load adjusted per R. Hill to 49, life safety finaled.
FIR08-00130 INSP-Supply line flush5/1/20085/2/20085/2/2008 3:45:50 PMPPART
UG fire supply line flush completed satisfactory.
FIR08-00236 INSP-Final Inspection5/1/20085/2/20085/2/2008 2:36:59 PMANH
Contractor not on site, plans need to be available for inspection, rescheduled site visit with contact per phone conversation.
BLD06-00195 FIRE-Final Inspection5/1/20085/2/20085/2/2008 1:15:42 PMAPASS
Life safety inspection completed acceptable pending the installation of lever hardware at the second exit door-to be verified at the structural final per agreement with contractor.
FIR06-00595 INSP-Final Inspection5/1/20085/2/20085/2/2008 12:03:44 PMADEFR
Scheduled by a contractor via Hello! on 5/1/2008 at 5:20:41 PM. Contact: ###-####.
BLD07-01091 FIRE-Final Inspection5/1/20085/2/20085/2/2008 12:02:50 PMAPASS
NOTE: fire sprinkler and fire alarm work for this area completed under BLD07-01692 project related FIR #'s. Fire life safety inspection passed.
BLD07-01692 FIRE-Final Inspection5/1/20085/2/20085/2/2008 11:58:28 AMAPART
Fire life safety is satisfactory for the areas inspected today including the sat. pharmacy, work room and anesthesia soils room, door seals installed while on site, one noted fire sprinkler head at the pharmacy has been added, adjacent fire doors at the corridor to be adjusted as discussed with contractor.
FIR08-00068 INSP-Sprinkler Rough-in5/1/20085/2/20085/2/2008 11:02:06 AMAPART
Inspection completed for hard lid areas finished to date, okayed for cover storage rooms 129A, 108A, work room 128, mens restrooms 147 and 148, womens restroom 145. NOTE: no approval for cover at womens restroom 149 due to missing hanger at the arm-over to the pendent head, see stamped plan set for annotations.
FIR07-01041 INSP-Sprinkler Rough-in/Hydro5/1/20085/2/20085/2/2008 10:57:44 AMACANC
Scheduled by a contractor via Hello! on 5/1/2008 at 12:02:49 PM. Contact: ###-####. Inspection rescheduled per phone conversation with contractor.
FIR08-00066 INSP-Sprinkler Rough-in5/1/20085/2/20085/2/2008 10:56:39 AMAPART
See approved plans for areas previously marked as okay for cover-no new hard lids to inspect at this time, new south entrance vestibule is not yet piped, be aware of possible obstructions/spacing issues at the front soffits depending on drop ceiling heights and head locations.