Inspections for the day of: Monday, May 2, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00577 FIR-Aging Inspection5/2/20115/2/20115/5/2011 9:16:37 AM NR
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
BLD11-00671 FIRE-Final Inspection5/2/20115/2/20115/2/2011 3:31:36 PMPFAIL
Column protection has not been provided per IFC chapter 23 and NFPA 13 6.1.4.1. The commodity has been classified as up to IV but the density will provide for a class III per the chapter 16 table.
BLD11-00678 FIRE-Final Inspection4/29/20115/2/20115/2/2011 11:22:11 AMAPASS
life safety passed
BLD09-02034 FIRE-Final Inspection4/29/20115/2/20115/2/2011 10:45:34 AMAFAIL
Provide the additional fire extinguisher as discussed and provide the single action hardware on the new doors as discussed.
BLD11-00425 FIRE-Final Inspection4/28/20115/2/20115/2/2011 8:38:59 AMAFAIL
Dustin Phone #: ###-#### Called contact and left message on phone. Stopped at project which was locked with no access. No inspection performed.