FIR10-00577
| FIR-Aging Inspection | 5/2/2011 | 5/2/2011 | 5/5/2011 9:16:37 AM | | NR |
|
|
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
|
BLD11-00671
| FIRE-Final Inspection | 5/2/2011 | 5/2/2011 | 5/2/2011 3:31:36 PM | P | FAIL |
|
|
Column protection has not been provided per IFC chapter 23 and NFPA 13 6.1.4.1. The commodity has been classified as up to IV but the density will provide for a class III per the chapter 16 table.
|
BLD11-00678
| FIRE-Final Inspection | 4/29/2011 | 5/2/2011 | 5/2/2011 11:22:11 AM | A | PASS |
|
|
life safety passed
|
BLD09-02034
| FIRE-Final Inspection | 4/29/2011 | 5/2/2011 | 5/2/2011 10:45:34 AM | A | FAIL |
|
|
Provide the additional fire extinguisher as discussed and provide the single action hardware on the new doors as discussed.
|
BLD11-00425
| FIRE-Final Inspection | 4/28/2011 | 5/2/2011 | 5/2/2011 8:38:59 AM | A | FAIL |
|
|
Dustin Phone #: ###-#### Called contact and left message on phone. Stopped at project which was locked with no access. No inspection performed.
|