Inspections for the day of: Friday, May 2, 2014.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00443 ELE-Aging Inspection5/2/20145/2/20145/2/2014 2:57:57 PM DONE
Still under construction
ELE12-02127 ELE-Aging Inspection5/2/20145/2/20145/2/2014 2:54:25 PM DONE
Still under construction
ELE10-01638 ELE-Aging Inspection5/2/20145/2/20145/2/2014 2:20:27 PM DONE
Still Under construction
ELE14-00884 Final5/2/20145/2/20145/2/2014 2:17:30 PMPPASS
Dan Phone #: ###-#### Final ok
ELE14-00883 Final5/2/20145/2/20145/2/2014 2:03:30 PMPNR
Dan Phone #: ###-#### Show window and exit on east side not complete.
ELE14-00883 Electrical Rough-In5/2/20145/2/20145/2/2014 1:38:13 PMPPART
Dan Phone #: ###-#### East tiles will be lift out so can inspect exit and show window boxes. Rest of ceiling rough in ok cover
ELE14-00829 Final5/2/20145/2/20145/2/2014 1:16:33 PMPPASS
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER Final ok
ELE13-03533 Final5/2/20145/2/20145/2/2014 12:41:13 PMPPASS
vince Phone #: ###-#### Final ok
ELE14-01011 Final5/1/20145/2/20145/2/2014 10:48:01 AMAPASS
Crescent rim Condos unit 2-303
Gil ###-#### Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Final ok
ELE14-01010 Final5/1/20145/2/20145/2/2014 10:42:40 AMAPASS
Crescent Rim Condos unit 3-404
Gil ###-#### Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Final ok
ELE14-01095 Electrical Rough-In5/1/20145/2/20145/2/2014 10:10:44 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Idaho power requires an expansion joint on all underground service entrance conduits for residential.
250.52(B)(1)- Metal gas piping systems shall not be used as grounding electrodes. 250.104(B) not enforced in Idaho.
334.30- NM cable shall be secured with in 12" of box.
210.52- Up bedroom, any wall space 24" and wider shall have receptical outlet installed.
ELE14-01100 Conference5/1/20145/2/20145/2/2014 9:29:42 AMADONE
Gregory-please call to meet Phone #: ###-#### Discussed code changes between 100 and 200 amp services.
ELE13-01492 Final5/1/20145/2/20145/2/2014 9:00:44 AMAPASS
>> Inspection requested via web by shane miller Final ok
ELE14-00860 Electrical Rough-In5/2/20145/2/20145/2/2014 8:39:26 AMAPASS
exterior lights Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Exterior lighting on north, east, south sides and new cooler rough in ok cover