Inspections for the day of: Wednesday, May 2, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF17-00083 INSP-Final4/30/20185/2/20185/7/2018 2:08:29 PMAFAIL
Provide separate permit for the second tenant, provide separate permit for the racking over 8' in height, provide fire extinguisher on mezzanine, remove all deadbolts on all exits except at the main exit as discussed.

Call prior to going Phone #: 2083369860 >> Inspection requested via mobile web by Todd Weltner
FIR18-00244 INSP-Final Inspection4/30/20185/2/20185/3/2018 1:30:10 PMPPART
Functionality fo the sppression system tested. As-builts received. Will be able to final when a life safety inspection is passed for the paint booth itself.

Nate Phone #: ###-####
BLD17-01479 FIRE-Final Inspection5/2/20185/2/20185/2/2018 2:05:23 PMPPASS
Life safety passed

Greg Phone #: ###-####
FIR17-00452 INSP-Final Inspection5/1/20185/2/20185/2/2018 2:04:58 PMPPASS
Permit finaled
FIR17-00479 INSP-Final Inspection5/1/20185/2/20185/2/2018 2:04:35 PMPPASS
Permit finaled
FIR17-00483 INSP-Final Inspection5/1/20185/2/20185/2/2018 2:04:18 PMPPASS
Permit finaled
FIR17-00448 INSP-Final Inspection5/1/20185/2/20185/2/2018 2:03:57 PMPPASS
Permit finaled
FIR17-00446 INSP-Final Inspection5/1/20185/2/20185/2/2018 1:08:57 PMPPASS
Permit finaled
FIR17-00478 INSP-Final Inspection5/1/20185/2/20185/2/2018 1:08:36 PMPPASS
Permit finaled
FIR17-00477 INSP-Final Inspection5/1/20185/2/20185/2/2018 1:08:17 PMPPASS
Permit finaled
FIR17-00447 INSP-Final Inspection5/1/20185/2/20185/2/2018 1:07:57 PMPPASS
Permit finaled
BLD17-01277 FIRE-Final Inspection5/1/20185/2/20185/2/2018 10:51:10 AMAFAIL
For a life safety final I need the sprinkler coverage and door hardware issues corrected on the ground floor as noted on the plans.

Julio Phone #: ###-####