ELE19-01354
| Electrical Rough-In | 5/2/2019 | 5/2/2019 | 5/2/2019 3:02:51 PM | P | PASS |
|
|
Joshua Phone #: ###-#### Basement only ok to cover
|
ELE19-01532
| Final | 5/2/2019 | 5/2/2019 | 5/2/2019 3:02:22 PM | P | PASS |
|
|
Dean Phone #: ###-#### Occ card onsite and not signed by any other being it wasn't on site to be signed at that time Final ok
|
ELE19-01597
| Electrical Rough-In | 5/1/2019 | 5/2/2019 | 5/2/2019 2:05:09 PM | P | FAIL |
|
|
Inspection requested via web by Dan Hobdey 334.30Type NM cable shall be supported in intervals not exceeeding 4 1/2'(in garage) 314.28(c) all j-boxes shall provide a cover(up bonus room)
|
ELE19-00724
| Final | 5/2/2019 | 5/2/2019 | 5/2/2019 1:31:19 PM | P | PASS |
|
|
AJ Phone #: ###-#### Occ card signed Final ok
|
ELE19-01599
| Electrical Rough-In | 5/2/2019 | 5/2/2019 | 5/2/2019 1:30:47 PM | P | PASS |
|
|
Pool bonding re-inspect Proper U/L listed connetors installed, 6 points stubbed out for bonding all 4 corners done and misc bonds
|
ELE19-01599
| Electrical Rough-In | 5/1/2019 | 5/2/2019 | 5/2/2019 11:43:20 AM | A | FAIL |
|
|
We need an electrical inspection for underground electrical and rebar so the pool can be covered. Thank you Phone #: ###-#### Inspection requested via web by Angela Stears 110.3 Products used shall be U/L listed and marked for direct burial(ground clamps are not marked)
|
ELE19-00774
| Final | 5/1/2019 | 5/2/2019 | 5/2/2019 11:06:37 AM | A | FAIL |
|
|
Ant questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren 210.63 Air conditionning equipment shall have a receptacle located within 25' of equipment 408.36(d) Back fed devices shall be secured in place 250.94(a) Intersystem bond device required
|
ELE19-01123
| Electrical Rough-In | 5/1/2019 | 5/2/2019 | 5/2/2019 10:05:02 AM | A | PASS |
|
|
We need an underground inspection, Pat is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Secondary conduits to switch gear ok to cover
|
ELE19-00938
| Final | 5/1/2019 | 5/2/2019 | 5/2/2019 9:44:11 AM | A | PASS |
|
|
For access please call Ed 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott 210.8 All receptacle located within 6' of a sink shall have GFCI protection(receptacle right of island sink on wall) 110.25 Hard wired appilances shall means of lockable disc.
|
ELE19-01169
| Final | 5/1/2019 | 5/2/2019 | 5/2/2019 8:20:06 AM | A | CANC |
|
|
Darin- please call for access Phone #: ###-#### Inspection cancelled from web by: Rob Maes
|