Inspections for the day of: Thursday, May 2, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01354 Electrical Rough-In5/2/20195/2/20195/2/2019 3:02:51 PMPPASS
Joshua Phone #: ###-####
Basement only ok to cover
ELE19-01532 Final5/2/20195/2/20195/2/2019 3:02:22 PMPPASS
Dean Phone #: ###-####
Occ card onsite and not signed by any other being it wasn't on site to be signed at that time
Final ok
ELE19-01597 Electrical Rough-In5/1/20195/2/20195/2/2019 2:05:09 PMPFAIL
Inspection requested via web by Dan Hobdey
334.30Type NM cable shall be supported in intervals not exceeeding 4 1/2'(in garage)
314.28(c) all j-boxes shall provide a cover(up bonus room)
ELE19-00724 Final5/2/20195/2/20195/2/2019 1:31:19 PMPPASS
AJ Phone #: ###-####
Occ card signed
Final ok
ELE19-01599 Electrical Rough-In5/2/20195/2/20195/2/2019 1:30:47 PMPPASS
Pool bonding re-inspect
Proper U/L listed connetors installed, 6 points stubbed out for bonding all 4 corners done and misc bonds
ELE19-01599 Electrical Rough-In5/1/20195/2/20195/2/2019 11:43:20 AMAFAIL
We need an electrical inspection for underground electrical and rebar so the pool can be covered. Thank you Phone #: ###-#### Inspection requested via web by Angela Stears
110.3 Products used shall be U/L listed and marked for direct burial(ground clamps are not marked)
ELE19-00774 Final5/1/20195/2/20195/2/2019 11:06:37 AMAFAIL
Ant questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
210.63 Air conditionning equipment shall have a receptacle located within 25' of equipment
408.36(d) Back fed devices shall be secured in place
250.94(a) Intersystem bond device required
ELE19-01123 Electrical Rough-In5/1/20195/2/20195/2/2019 10:05:02 AMAPASS
We need an underground inspection, Pat is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Secondary conduits to switch gear ok to cover
ELE19-00938 Final5/1/20195/2/20195/2/2019 9:44:11 AMAPASS
For access please call Ed 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott
210.8 All receptacle located within 6' of a sink shall have GFCI protection(receptacle right of island sink on wall)
110.25 Hard wired appilances shall means of lockable disc.
ELE19-01169 Final5/1/20195/2/20195/2/2019 8:20:06 AMACANC
Darin- please call for access Phone #: ###-#### Inspection cancelled from web by: Rob Maes