Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00476 INSP-Final Inspection5/19/20035/20/20035/20/2003 12:00:00 AMACANC
canceled at the fire alarm contractors request until next tuesday at 7:30 am 5/20/2003 12:07:56 PM
FIR03-00055 INSP-Final Inspection5/19/20035/20/20035/20/2003 12:00:00 AMAFAIL
provide map for facp, the duct smoke detector for the shut down of the hvac unit has been removed. Provide verification that the detector is not required per UMC 608 5/20/2003 12:07:15 PM
BLD03-00446 FIRE-Conference5/20/20035/20/20035/20/2003 12:00:00 AMPDONE
spoke with the contractor about fire extinguisher placement 5/20/2003 4:20:17 PM
BLD02-01148 FIRE-Final Inspection5/20/20035/20/20035/20/2003 12:00:00 AMPFAIL
install the missing canopies on the sprinkler pendants, move the foosball table that is obstructing the exit door, provide city approved fire sprinkler plans per review note #1, provide verification that a fire sprinkler monitoring system is not required, provide building address per review note #5, post sign at point of entry per review note #4, the fire extinguisher in classroom 101 is mounted too high see review note #6, provide information for cfm ratings on the hvac units for compliance with review note #30 and UMC 608, no storage allowed on the mezzanine per the scope of work comments. 5/20/2003 4:27:07 PM
BLD02-00311 FIRE-Final Inspection5/13/20035/20/20035/20/2003 12:00:00 AMPPART
See approved fire sprinkler plans for areas where occupancy is allowed 5/20/2003 4:28:27 PM
FIR02-00359 INSP-Final Inspection5/13/20035/20/20035/20/2003 12:00:00 AMPPART
###-#### See approved alarm for exact locations that have been approved with todays date. Area was around elevator #2 5/20/2003 2:30:48 PM