ELE05-01774
| Electrical Rough-In | 5/20/2005 | 5/20/2005 | 5/20/2005 4:34:49 PM | P | CANC |
|
|
###-#### - clyde called, left message, wrong house and permit,no job id sticker
|
ELE05-00416
| Final | 5/20/2005 | 5/20/2005 | 5/20/2005 4:19:40 PM | P | NR |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner to have all rcpts and a/c wired so we can final. will call later
|
ELE04-03595
| Final | 5/20/2005 | 5/20/2005 | 5/20/2005 3:13:35 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/20/2005 at 9:32:46 AM. Contact: ###-####. called contr, left corr notice, 110.26(A) work space shall be provided about equipment, 110.3(A)(1) recpts shall be suitable at installation to allow covers to o
|
ELE05-01760
| Electrical Rough-In | 5/20/2005 | 5/20/2005 | 5/20/2005 2:42:59 PM | P | FAIL |
|
|
george; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left message, left corr notice, 362.26 there shall be no more than 360 degree bends, 362.24 bend radius too tight
|
ELE05-01468
| Final | 5/20/2005 | 5/20/2005 | 5/20/2005 1:54:22 PM | P | CANC |
|
|
potting pool inspection//chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see cloned insp
|
ELE05-01048
| Final | 5/20/2005 | 5/20/2005 | 5/20/2005 1:28:45 PM | P | PASS |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-01572
| Temporary Service | 5/20/2005 | 5/20/2005 | 5/20/2005 12:19:45 PM | P | FAIL |
|
|
clyde; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left message,250.24(A) gec shall be connected to grounded service conductor. fee due, left correction notice
|
ELE05-01769
| Electrical Rough-In | 5/19/2005 | 5/20/2005 | 5/20/2005 10:26:44 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see clone insp
|
ELE05-00923
| Electrical Rough-In | 5/19/2005 | 5/20/2005 | 5/20/2005 10:12:34 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 5/19/2005 at 8:36:08 PM. Contact: ###-####. told owner to mount boxes for outside lites and recpts, and to make up all wiring. said he could temp insulation only due to temps required for floor. wiring in
|
ELE05-01682
| Electrical Rough-In | 5/19/2005 | 5/20/2005 | 5/20/2005 9:21:23 AM | A | PASS |
|
|
ceiling cover inspection thanks; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ceiling cover ok
|
ELE05-01069
| Final | 5/19/2005 | 5/20/2005 | 5/20/2005 9:09:02 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/19/2005 at 5:11:46 PM. Contact: ###-####. ok to final
|
ELE05-00913
| Final | 5/19/2005 | 5/20/2005 | 5/20/2005 8:24:24 AM | A | PASS |
|
|
darrell ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr about 2 recpts, ok to final
|
ELE05-00353
| Final | 5/20/2005 | 5/20/2005 | 5/20/2005 8:00:04 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/20/2005 at 6:54:28 AM. Contact: ###-####. ok to final
|
ELE05-01769
| Rough-In Permanent Service | 5/20/2005 | 5/20/2005 | 5/20/2005 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, left survey, left message, 312.5 shall protect cable from abrasion, job id shall be posted
|
ELE05-01769
| Rough-In Permanent Service | 5/20/2005 | 5/20/2005 | 5/20/2005 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, left survey, left message, 312.5 shall protect cable from abrasion, job id shall be posted. ric ok , p/s u/g n ok
|
ELE05-01468
| Electrical Rough-In | 5/20/2005 | 5/20/2005 | 5/20/2005 12:00:00 AM | P | PASS |
|
|
potting pool inspection//chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa potting ok for pool and hot tub
|