FIR05-00196
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 4:41:20 PM | P | CANC |
|
|
Cancel inspection per. Rick Jackson, not ready.
|
FIR04-00657
| INSP-Final Inspection | 5/18/2005 | 5/20/2005 | 5/20/2005 3:24:42 PM | P | PART |
|
|
Farmers and Merchants Bank spaces on the basement, first, and second floors passed fire alarm inspection. Revised plans need to reflect additional HS in basement elevator lobby, actual location of heat pump now in men's room, correct cd rating on HS in f
|
FIR04-00811
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 3:06:21 PM | P | FAIL |
|
|
Remove fire sprinkler canopy at front entry first floor that has been used as a coverplate for a previously used hole. Inadequate sprinkler coverage in basement bank vault as installed, heads are overspaced off wall.
|
FIR04-00807
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 3:00:22 PM | P | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00047
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 2:59:47 PM | P | PASS |
|
|
Fire sprinkler finaled.
|
BLD04-01885
| FIRE-Alarm Testing | 5/19/2005 | 5/20/2005 | 5/20/2005 12:28:37 PM | A | CANC |
|
|
Cancel per. Dave, the general contractor. Duplicate inspection.
|
BLD04-01885
| FIRE-Final Inspection | 5/19/2005 | 5/20/2005 | 5/20/2005 12:24:44 PM | A | FAIL |
|
|
Fail inspection due to several issues, all of which are indicated on the correction notice. Some items are; install fire ext. in basement and 2nd floors, provide suite address, verify door hardware not yet installed, provide approved hardware on teller d
|
FIR05-00045
| INSP-Sprinkler Rough-in | 5/19/2005 | 5/20/2005 | 5/20/2005 10:07:11 AM | A | CANC |
|
|
Cancel inspection per. Tom Easton at Grinnell. Duplicate inspection, this inspection already completed the previous day.
|
FIR05-00052
| INSP-Alarm Testing | 5/20/2005 | 5/20/2005 | 5/20/2005 12:00:00 AM | P | PART |
|
|
Farmers and Merchants bank spaces in basement, first, and second floors passed fire alarm inspection. Revised plans need to reflect additional HS in basement elevator lobby, actual location of heat pump in men's room, correct cd of HS in first floor office.
|