Inspections for the day of: Friday, May 20, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00261 INSP-Sprinkler Rough-in5/20/20055/20/20055/20/2005 4:17:00 PMPPASS
Rough-in passed. Still need to final shell permit
FIR05-00241 INSP-Sprinkler Rough-in5/19/20055/20/20055/20/2005 4:15:04 PMPFAIL
no approved plans on site. Will need separation between warehouse and office or uprights over office re-installed
BLD04-01600 FIRE-Final Inspection5/20/20055/20/20055/20/2005 3:32:44 PMPPASS
Fire life safety finaled
FIR04-00761 INSP-Final Inspection5/20/20055/20/20055/20/2005 2:52:24 PMPPASS
Fire sprinkler finaled
FIR05-00015 INSP-Final Inspection5/20/20055/20/20055/20/2005 2:50:22 PMPPASS
fire alarm finaled
BLD05-00736 FIRE-Final Inspection5/20/20055/20/20055/20/2005 2:09:49 PMPFAIL
Went over life safety items with the contractor which included venting between warehouse and sales area for the smoke exhaust sytem, correct door hardware, tags on fire extinguishers and testing of the exit signs and emergency lights. Need to test the smo
FIR05-00267 INSP-Final Inspection5/20/20055/20/20055/20/2005 2:06:43 PMPFAIL
Resubmit plans showing the correct floor plan, main location, piping size and deletion of head at front of store. Provide sprinkler coverage in the entry since entry soffit and overhead duct combined exceed 4'.
BLD05-00288 FIRE-Final Inspection5/19/20055/20/20055/20/2005 2:04:42 PMAFAIL
Provide exit discharge lighting (if this is the only item left I can sign a temp per Sam Rogers), repair the two office exit lights, provide manual operation for the smoke vents per IFC 910.3.1
BLD04-02121 FIRE-Final Inspection5/19/20055/20/20055/20/2005 2:04:15 PMAFAIL
Provide exit discharge lighting (if this is the only item left I can sign a temp per Sam Rogers), repair the two office exit lights, provide manual operation for the smoke vents per IFC 910.3.1
FIR05-00068 INSP-Sprinkler Rough-in5/19/20055/20/20055/20/2005 11:03:48 AMAPART
Sprinkler piping fo rthe most part is ok. See city approved plans for locations of deficiecies which include missing hangers, modified routing of piping, deletion of heads and additional heads to be required under duct work in the auditorium. Plans will n
BLD05-00395 FIRE-Final Inspection5/20/20055/20/20055/20/2005 8:45:22 AMAFAIL
Could not final fire sprinkler permit therefore no final on the life safety.
FIR05-00097 INSP-Final Inspection5/19/20055/20/20055/20/2005 8:44:32 AMAFAIL
Two pendants off of a single 1" outlet in one location immediately inside of the entry way.
BLD05-00224 FIRE-Final Inspection5/20/20055/20/20055/20/2005 8:43:42 AMAPASS
Fire life safety finaled
FIR05-00065 INSP-Final Inspection5/19/20055/20/20055/20/2005 8:42:40 AMAPASS
Fire sprinkler finaled
FIR05-00241 INSP-Sprinkler Rough-in5/19/20055/20/20055/19/2005 3:11:33 PMPCANC
This is a rough in for Cypress/Budget Blinds. Mike is the contact for this.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice