FIR05-00261
| INSP-Sprinkler Rough-in | 5/20/2005 | 5/20/2005 | 5/20/2005 4:17:00 PM | P | PASS |
|
|
Rough-in passed. Still need to final shell permit
|
FIR05-00241
| INSP-Sprinkler Rough-in | 5/19/2005 | 5/20/2005 | 5/20/2005 4:15:04 PM | P | FAIL |
|
|
no approved plans on site. Will need separation between warehouse and office or uprights over office re-installed
|
BLD04-01600
| FIRE-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 3:32:44 PM | P | PASS |
|
|
Fire life safety finaled
|
FIR04-00761
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 2:52:24 PM | P | PASS |
|
|
Fire sprinkler finaled
|
FIR05-00015
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 2:50:22 PM | P | PASS |
|
|
fire alarm finaled
|
BLD05-00736
| FIRE-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 2:09:49 PM | P | FAIL |
|
|
Went over life safety items with the contractor which included venting between warehouse and sales area for the smoke exhaust sytem, correct door hardware, tags on fire extinguishers and testing of the exit signs and emergency lights. Need to test the smo
|
FIR05-00267
| INSP-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 2:06:43 PM | P | FAIL |
|
|
Resubmit plans showing the correct floor plan, main location, piping size and deletion of head at front of store. Provide sprinkler coverage in the entry since entry soffit and overhead duct combined exceed 4'.
|
BLD05-00288
| FIRE-Final Inspection | 5/19/2005 | 5/20/2005 | 5/20/2005 2:04:42 PM | A | FAIL |
|
|
Provide exit discharge lighting (if this is the only item left I can sign a temp per Sam Rogers), repair the two office exit lights, provide manual operation for the smoke vents per IFC 910.3.1
|
BLD04-02121
| FIRE-Final Inspection | 5/19/2005 | 5/20/2005 | 5/20/2005 2:04:15 PM | A | FAIL |
|
|
Provide exit discharge lighting (if this is the only item left I can sign a temp per Sam Rogers), repair the two office exit lights, provide manual operation for the smoke vents per IFC 910.3.1
|
FIR05-00068
| INSP-Sprinkler Rough-in | 5/19/2005 | 5/20/2005 | 5/20/2005 11:03:48 AM | A | PART |
|
|
Sprinkler piping fo rthe most part is ok. See city approved plans for locations of deficiecies which include missing hangers, modified routing of piping, deletion of heads and additional heads to be required under duct work in the auditorium. Plans will n
|
BLD05-00395
| FIRE-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 8:45:22 AM | A | FAIL |
|
|
Could not final fire sprinkler permit therefore no final on the life safety.
|
FIR05-00097
| INSP-Final Inspection | 5/19/2005 | 5/20/2005 | 5/20/2005 8:44:32 AM | A | FAIL |
|
|
Two pendants off of a single 1" outlet in one location immediately inside of the entry way.
|
BLD05-00224
| FIRE-Final Inspection | 5/20/2005 | 5/20/2005 | 5/20/2005 8:43:42 AM | A | PASS |
|
|
Fire life safety finaled
|
FIR05-00065
| INSP-Final Inspection | 5/19/2005 | 5/20/2005 | 5/20/2005 8:42:40 AM | A | PASS |
|
|
Fire sprinkler finaled
|
FIR05-00241
| INSP-Sprinkler Rough-in | 5/19/2005 | 5/20/2005 | 5/19/2005 3:11:33 PM | P | CANC |
|
|
This is a rough in for Cypress/Budget Blinds. Mike is the contact for this.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|