Inspections for the day of: Tuesday, May 20, 2008.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00893 Final5/20/20085/20/20085/20/2008 3:47:35 PMAPART
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok bad gfci N end 3 bed rm unit
ELE08-01315 Electrical Rough-In5/20/20085/20/20085/20/2008 3:41:25 PMPPART
Neal ###-####///please call for access info
walls and u/g ok
ELE08-01268 Permanent Service5/20/20085/20/20085/20/2008 2:15:14 PMPPART
###-#### - corey ###-#### office when finished p/s u/g rec. ok
ELE08-01268 Final5/20/20085/20/20085/20/2008 2:14:55 PMPPASS
###-#### - corey ###-#### office when finished ok
ELE08-00956 Permanent Service5/19/20085/20/20085/20/2008 1:16:54 PMPPASS
This inspection is for a 200 amp service change on a home that is being remodeled. Tom ###-#### Phone #: ###-#### Internet Inspection Request from: Emmet Bushman
told contr about recept spacing for countertops in kit, p/s u/g rec. ok
ELE08-01307 Rough-In Permanent Service5/19/20085/20/20085/20/2008 12:40:58 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i ok
p/s u/g new ok
ELE08-01008 Final5/19/20085/20/20085/20/2008 11:40:57 AMAPASS
Patio cover lighting. Phone #: ###-#### Internet Inspection Request from: Lloyd Looney ok
ESC08-00330 Site Preparation5/20/20085/20/20085/20/2008 10:33:01 AMAPART
card posted
ELE08-01227 Electrical Rough-In5/19/20085/20/20085/20/2008 10:30:24 AMAFAIL
steve Phone #: ###-#### called corr update permit for 3 rms, 210.52(A&B) required outlet for old and new walls shall not use SABC for new office created from old din rm
ELE08-01244 Conference5/20/20085/20/20085/20/2008 10:28:45 AMADONE
300.4 nail plates and 11/4" for cables, 210.52(A&B) required outlets for wall space new and old wall of kit and liv rm, shall not use SABC for micro wave D W disposal , only what code allows shall be on SABC, 250.140 shall use 4 wire for new oven, 314.16 box fill adjustible boxes in kit, called
ESC08-00376 Site Preparation5/20/20085/20/20085/20/2008 10:24:37 AMAPART
card posted site ok
ELE08-01244 Electrical Rough-In5/19/20085/20/20085/20/2008 10:12:11 AMAFAIL
tony - please call for access Phone #: see added conference
ELE08-01295 Permanent Service5/19/20085/20/20085/20/2008 8:59:54 AMAPASS
re-inspection on 200amp permanent power pole Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe p/s o/h new ok
ELE08-01295 Final5/20/20085/20/20085/20/2008 8:59:38 AMAPASS
re-inspection on 200amp permanent power pole Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok
ELE08-00911 Final5/20/20085/20/20085/20/2008 8:23:27 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Surerus 210.52(A) needs outlet for wall space between bath and closet doors, check clearence closet fixture if it is incandescent, 410.8 also needs service change for proper size house calcs out over 100 amp contr said called
ELE08-01268 Final5/20/20085/20/20085/20/2008 7:47:13 AMANR
Electrical questions call Cory @ ###-####.
Upgraded 100 amp panel to 200 amp Phone #: ###-#### Internet Inspection Request from: Yolanda Morris called contr (cory) he will call for p/s when ready
ELE08-00626 ELE-Aging Inspection5/20/20085/20/20085/20/2008 7:25:27 AM DONE
wsuc
ELE08-00589 ELE-Aging Inspection5/20/20085/20/20085/20/2008 7:25:02 AM DONE
wsuc
ELE08-00657 ELE-Aging Inspection5/20/20085/20/20085/20/2008 7:24:26 AM DONE
wsuc
ELE08-01268 Electrical Rough-In5/19/20085/20/20085/19/2008 3:19:15 PMACANC
blanca Phone #: ###-#### Inspection cancelled from web by: Yolanda Morris