ESC08-00164
| General Inspection | 5/20/2008 | 5/20/2008 | 5/20/2008 4:16:21 PM | P | PASS |
|
|
looked ok
|
ESC08-00322
| General Inspection | 5/20/2008 | 5/20/2008 | 5/20/2008 4:14:29 PM | P | PASS |
|
|
looked ok
|
ELE08-01317
| Electrical Rough-In | 5/20/2008 | 5/20/2008 | 5/20/2008 4:12:59 PM | P | PASS |
|
|
Tim R/I-Conference Phone #: ###-#### talked with homeowner, ric ok
|
ELE08-01309
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 3:39:00 PM | P | PASS |
|
|
Jesse Phone #: ###-#### called contractor, ric ok,
|
ELE07-03786
| Final | 5/20/2008 | 5/20/2008 | 5/20/2008 2:05:39 PM | P | FAIL |
|
|
chris Phone #: ###-#### called contractor,left message, left correction notice, NEC 210.8(B) baths shall have gfci receptacles, 422.31(B) dishwasher shall be provided with disconnect, lockable,BCC shall follow approved plans for energy conservation-dual level switching for lighting, shall uncover floor box for u/g inspection or demo out, shall call for core and shell final before tenant final
|
ELE08-00705
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 1:26:47 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/19/2008 at 4:29:28 PM. Contact: ###-####. ok to cover u/g at guard shack area north east area parking lot
|
ELE08-01104
| Permanent Service | 5/20/2008 | 5/20/2008 | 5/20/2008 12:48:06 PM | P | PASS |
|
|
Internet Inspection Request from: BRENDA HURST checked job, done 5/2/08, called contractor, meter in socket
|
ELE08-01311
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 12:24:51 PM | P | PASS |
|
|
soffit will be ready for rough in for cover Tuesday afternoon thank you Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker talked to contractor, sign people will pull permits, added access holes to inspect later, ric ok for soffits
|
ELE08-01246
| Final | 5/19/2008 | 5/20/2008 | 5/20/2008 11:02:13 AM | A | PASS |
|
|
Please call homeowner before you go so he knows when you will be there. Upgraded panel 100 t0 200 amp. Already passed rough. Phone #: ###-#### Internet Inspection Request from: Yolanda Morris ok to final, called contractor
|
ELE08-01316
| Permanent Service | 5/20/2008 | 5/20/2008 | 5/20/2008 11:01:15 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
ELE07-02302
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 10:59:07 AM | A | PASS |
|
|
Contact Steve Hess. Ceiling grid inspection I & J. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to cover ceiling anop
|
ELE08-01302
| Permanent Service | 5/19/2008 | 5/20/2008 | 5/20/2008 10:41:33 AM | A | PASS |
|
|
andy Note: after 9:00 Phone #: ###-#### p/s o/h rec ok
|
ELE08-00900
| Electrical Rough-In | 5/20/2008 | 5/20/2008 | 5/20/2008 9:53:26 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 5/20/2008 at 6:07:24 AM. Contact: ###-####. ok to cover ceilings anop
|
ELE08-01010
| Final | 5/20/2008 | 5/20/2008 | 5/20/2008 9:34:21 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
|
ELE08-01312
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 9:03:18 AM | A | PASS |
|
|
Call ahead so I can verify entrance into home. Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contractor, ric kitchen walls ok
|
ELE08-01190
| Rough-In Permanent Service | 5/19/2008 | 5/20/2008 | 5/20/2008 8:39:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, called contractor, p/s u/g n ok
|
ELE08-01191
| Rough-In Permanent Service | 5/19/2008 | 5/20/2008 | 5/20/2008 8:23:49 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk called left correction notice, 210.52(A)(1)&(2) shall mount receptacles in 2' wall space and not over 6' from broken wall line such as door- see kitchen, living room, open area by hall, 314.16 box shall not be overfilled with conductors per calculations-living room, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 250.10 ground clamp shall be protected, BCC approved set of plans shall be on job
|
ELE07-01776
| Final | 5/20/2008 | 5/20/2008 | 5/20/2008 12:00:00 AM | P | CANC |
|
|
Call Joe if you need garage door code. Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt
|
ELE08-00705
| Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/19/2008 4:27:31 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 5/19/2008 at 9:53:22 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 19 2008 4:27PM.
|