Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01000 INSP-Final Inspection5/15/20085/20/20085/21/2008 2:55:59 PMPPASS
All six items per letter dated march 28, 2008 to Ken Howell have been resolved.KR
FIR04-00490 INSP-Final Inspection5/15/20085/20/20085/21/2008 2:54:57 PMPPASS
All six items per letter dated march 28, 2008 to Ken Howell have been resolved.KR
FIR07-00606 INSP-Sprinkler Rough-in/Hydro5/19/20085/20/20085/20/2008 5:43:32 PMPPART
Area J second floor classrooms only okayed for cover-four missing retaining straps attatched by an apprentice while on site, still need access above hard lids at the restrooms for inspection, upright heads at the RR mechanical chase need adjustment.
FIR08-00087 INSP-Final Inspection5/19/20085/20/20085/20/2008 5:32:29 PMPFAIL
Need to provide an updated map at the panel, SD at one DH is located too close to an HVAC grill, sample and vent tubes for all duct detectors must be installed and oriented per manufacturers instructions and data sheets.
BLD07-02934 FIRE-Final Inspection5/20/20085/20/20085/20/2008 12:42:05 PMPFAIL
Door hardware at two locations (restroom, suite 104 exit) is not approved, missing signage at the main entry/exit door- "door to remain unlocked......" see fire code review notes item #5, need to provide a current annual certification tag for the PFE-see review notes item #3 and plan annotations for details, missing suite address numbers per permit documents-existing building suite number is 300.
BLD07-02583 FIRE-Final Inspection5/20/20085/20/20085/20/2008 12:00:04 PMPFAIL
Fire code review notes indicate the existing non-required fire suppression system if removed shall require a demo permit. Noted system has been deleted without issuance of a permit. Also need to provide a current inspection/certification tag for the fire extinguisher, remainder of life safety is satisfactory.
FIR08-00125 FIR-Aging Inspection5/20/20085/20/20085/20/2008 11:29:28 AM DEFR
Pending site inspection request.
BLD07-03155 FIRE-Final Inspection5/19/20085/20/20085/20/2008 11:28:25 AMACANC
Scheduled by a contractor via Hello! on 5/19/2008 at 5:50:09 PM. Contact: ###-####. NOTE: Wrong inspection type called in........needed structural final. Permit details do not indicate any fire inspection signatures are required. Notified project contact to reschedule.
FIR08-00257 INSP-Sprinkler Rough-in5/19/20085/20/20085/20/2008 11:23:23 AMANR
Inspection request type is not accurate, need to coordinate schedule to accomodate tenant per contractor, site visit rescheduled per conversation.