Inspections for the day of: Wednesday, May 20, 2009.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00092 INSP-Final Inspection5/20/20095/20/20095/21/2009 3:23:08 PMPCANC
To be rescheduled for next wednesday per Alarmco
FIR09-00086 INSP-Final Inspection5/20/20095/20/20095/21/2009 3:22:51 PMPCANC
To be rescheduled for next wednesday per Alarmco
FIR09-00089 INSP-Final Inspection5/20/20095/20/20095/21/2009 3:22:33 PMPCANC
To be rescheduled for next wednesday per Alarmco.
FIR09-00069 FIR-Aging Inspection5/20/20095/20/20095/21/2009 1:18:29 PM NR
work is in progress
FIR05-00750 INSP-Final Inspection5/20/20095/20/20095/20/2009 4:41:31 PMPCANC
To be rescheduled due to being overbooked.
FIR08-00786 INSP-Alarm Testing5/20/20095/20/20095/20/2009 4:36:59 PMPCANC
To be rescheduled due to being overbooked.
BLD06-00845 FIRE-Final Inspection5/20/20095/20/20095/20/2009 4:36:38 PMPCANC
To be rescheduled due to being overbooked.
FIR08-00839 INSP-Sprinkler Rough-in5/19/20095/20/20095/20/2009 4:36:14 PMACANC
To be rescheduled due to being overbooked.
BLD08-01210 FIRE-Final Inspection5/19/20095/20/20095/20/2009 4:34:34 PMPFAIL
The project related fire alarm and fire sprinkler permits need to be finaled. Also the Area of Refuge items as listed on the fire and building review comments have not been addressed. One exit sign needs to be added on the roof stair entrance.
FIR09-00133 INSP-Sprinkler Rough-in/Hydro5/20/20095/20/20095/20/2009 4:32:09 PMPPASS
The hydro tests for the wet and dry systems passed. The sprinkler piping above the tile ceilings can be covered.
FIR09-00179 INSP-Sprinkler Rough-in/Hydro5/20/20095/20/20095/20/2009 4:18:36 PMPPASS
The above ground hydro test passed. The sprinkler piping above the layin tile can be coverd.
BLD08-02488 FIRE-Final Inspection5/19/20095/20/20095/20/2009 4:16:10 PMPFAIL
The life safety will be ok to pass when the project related fire sprinkler permit is passed
FIR09-00101 INSP-Final Inspection5/19/20095/20/20095/20/2009 4:13:59 PMAFAIL
There is a Storage Room 130 as shown on the approved building plans that has wood racks recently built. The sprinkler pendants exceed the maximum 130 sq. ft. per head allowed for ordinary hazard which this room would be considered. As-builts are required but resubmittals won't be. Also the minimum 18" clearance is not available due to the top shelf of these racks. Per discussion with the property manager the top rack will be removed.
FIR09-00189 INSP-Sprinkler Rough-in5/19/20095/20/20095/20/2009 2:48:43 PMAPART
The underground piping installed is 1 1/4" cpvc. Per the approved plans, note #4, if the piping is not poly then resubmittals are required. I contacted bruce about this but gave him the ok to cover. It also appears that the underground supply is coming up closer to the exterior wall than what is shown on the plans. This too will need to be addressed.
FIR09-00327 INSP-Final Inspection5/19/20095/20/20095/20/2009 1:49:27 PMAFAIL
Could not final since the sheet rock ceiling needs to be replaced at the new pendant head. The sprinkler piping can be covered.
FIR08-00832 INSP-Sprinkler Rough-in/Hydro5/18/20095/20/20095/20/2009 12:57:23 PMPPASS
The insulation has been installed on the second floor of building C and can be covered with sheet rock. I notified Mike, the superintendant.
BLD06-02169 FIRE-Conference5/19/20095/20/20095/20/2009 11:02:13 AMPDONE
I spoke to Brian with CM Company and he stated that he would follow up on the status.
FIR09-00027 INSP-Sprinkler Rough-in/Hydro5/19/20095/20/20095/20/2009 10:30:59 AMAPASS
Permit finaled
BLD08-01944 FIRE-Final Inspection5/19/20095/20/20095/20/2009 10:20:32 AMAFAIL
Provide fire dept access signage as discussed and provide an exit sign over the exterior breakroom door as shown on the approved plans. All other items ok.
FIR09-00027 INSP-Final Inspection5/19/20095/20/20095/20/2009 9:56:11 AMAPASS
Permit finaled
BLD08-00224 FIRE-Final Inspection5/20/20095/20/20095/20/2009 9:52:51 AMPPASS
Life safety passed. The fire alarm system as shown on the approved drawings has not been installed but it is not required either as per the project scope of work. This was discussed with Scott Arlenno.
FIR08-00679 INSP-Final Inspection5/19/20095/20/20095/20/2009 9:09:19 AMACANC
See yesterdays entry for details.
BLD08-02513 FIRE-Final Inspection5/19/20095/20/20095/20/2009 8:38:49 AMAFAIL
The revised plans showing the additional offices was not available on site. No inspection was performed.