BLD08-00264
| FIRE-Final Inspection | 5/18/2010 | 5/18/2010 | | P | |
|
|
Jim phone #: ###-####
|
BLD10-00622
| FIRE-Final Inspection | 5/20/2010 | 5/20/2010 | 5/20/2010 3:45:10 PM | P | PASS |
|
|
Fire life safety finaled, inspection passed.
|
FIR10-00185
| INSP-Final Inspection | 5/20/2010 | 5/20/2010 | 5/20/2010 3:38:53 PM | P | PASS |
|
|
|
BLD09-00777
| FIRE-Final Inspection | 5/20/2010 | 5/20/2010 | 5/20/2010 3:36:43 PM | P | FAIL |
|
|
Missing max. occupant load signs at three rooms per review note #8, hardware at both restroom doors is not approved, need access provided to the second floor level- one fire extinguisher req. at the 2nd floor, post tactile exit sign per plan annotations. EM and exit signs tested okay.
|
FIR10-00213
| INSP-Final Inspection | 5/18/2010 | 5/20/2010 | 5/20/2010 3:31:38 PM | A | FAIL |
|
|
Post indicator valve must be electronically supervised per IFC requirements. Approved plans also indicate a tamper switch at the PIV- final pending corrections. Remiander of work tested satisfactory, netcon rated 5 at the time of inspection.
|