BLD11-00933
| FIRE-Final Inspection | 5/19/2011 | 5/20/2011 | 5/20/2011 3:00:54 PM | A | FAIL |
|
|
Atleast one sprinkler head is overspaced at the east side of the door at the separation wall. This work will require a separate permit. Remove the deadbolt from the exit door at the top of the east stairwell. Repair all of the existing exit signs and emergency lights. Replace all of the missing ceiling tiles.
|
BLD11-00926
| FIRE-Conference | 5/19/2011 | 5/20/2011 | 5/20/2011 2:11:41 PM | A | DONE |
|
|
I went over life safety requirements with todd that included door hardware, exit signs/emergency lighting and possible new FIR permit for the hood suppression system.
|
FIR11-00206
| INSP-Final Inspection | 5/20/2011 | 5/20/2011 | 5/20/2011 1:21:54 PM | P | PASS |
|
|
Permit finaled
|
BLD11-00798
| FIRE-Final Inspection | 5/20/2011 | 5/20/2011 | 5/20/2011 1:21:28 PM | P | PASS |
|
|
life safety passed
|
FIR11-00209
| INSP-Sprinkler Rough-in | 5/19/2011 | 5/20/2011 | 5/20/2011 12:19:06 PM | A | PASS |
|
|
See approved plans for locations marked where the sprinkler piping can be covered.
|
BLD11-01014
| FIRE-Final Inspection | 5/19/2011 | 5/20/2011 | 5/20/2011 12:17:57 PM | A | FAIL |
|
|
Provide a 2A,10BC fire extinguisher with a current inspection tag, provide the correct sticker as discussed at the main exit, provide single action hardware and remove the deadbolt at the rear exit.
|
FIR11-00014
| INSP-Sprinkler Rough-in | 5/19/2011 | 5/20/2011 | 5/20/2011 9:45:18 AM | A | DONE |
|
|
The strobes in two additional exam rooms functioned correctly. Marked ok on the plans.
|