Inspections for the day of: Friday, May 20, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00933 FIRE-Final Inspection5/19/20115/20/20115/20/2011 3:00:54 PMAFAIL
Atleast one sprinkler head is overspaced at the east side of the door at the separation wall. This work will require a separate permit. Remove the deadbolt from the exit door at the top of the east stairwell. Repair all of the existing exit signs and emergency lights. Replace all of the missing ceiling tiles.
BLD11-00926 FIRE-Conference5/19/20115/20/20115/20/2011 2:11:41 PMADONE
I went over life safety requirements with todd that included door hardware, exit signs/emergency lighting and possible new FIR permit for the hood suppression system.
FIR11-00206 INSP-Final Inspection5/20/20115/20/20115/20/2011 1:21:54 PMPPASS
Permit finaled
BLD11-00798 FIRE-Final Inspection5/20/20115/20/20115/20/2011 1:21:28 PMPPASS
life safety passed
FIR11-00209 INSP-Sprinkler Rough-in5/19/20115/20/20115/20/2011 12:19:06 PMAPASS
See approved plans for locations marked where the sprinkler piping can be covered.
BLD11-01014 FIRE-Final Inspection5/19/20115/20/20115/20/2011 12:17:57 PMAFAIL
Provide a 2A,10BC fire extinguisher with a current inspection tag, provide the correct sticker as discussed at the main exit, provide single action hardware and remove the deadbolt at the rear exit.
FIR11-00014 INSP-Sprinkler Rough-in5/19/20115/20/20115/20/2011 9:45:18 AMADONE
The strobes in two additional exam rooms functioned correctly. Marked ok on the plans.