Inspections for the day of: Friday, May 20, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00269 ELE-Aging Inspection5/20/20115/20/20115/24/2011 2:45:07 PM PASS
still under construction
GCE11-00038 GCE-Final5/18/20115/20/20115/23/2011 8:35:16 AMAPASS
FinalPhil @ ###-####AM Inspection final ok
ELE11-01035 Rough-In Permanent Service5/20/20115/20/20115/20/2011 4:05:21 PMPFAIL
r/i and trench and service//Cal Phone #: ###-#### shall be no foreign piping above or below footprint of service panel
ELE11-00958 Rough-In Permanent Service5/20/20115/20/20115/20/2011 3:11:41 PMPFAIL
Please final if possible Phone #: ###-#### >> Inspection requested via web by Clint Tate Boise city code and Idaho Power require 2 in ridge or IMC for service swings for point of attachment
ELE11-00970 Final5/19/20115/20/20115/20/2011 2:19:26 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Celinda Winters NO identification tag,NEC250.64 Shalluse metallic conector listed for grounding and bonding or use non-metallic conector,NEC406.8A inuse covers missing,NEC406.8B weather resistant receptacles,Nec 352.10(F) Exsposed PVC conduit shall be schedule 80,NEC352.30(A) PVC conduit shall be fastened within 3ft of conduit termination.
ELE11-00961 Electrical Rough-In5/20/20115/20/20115/20/2011 9:54:39 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot
ELE11-00718 Final5/20/20115/20/20115/20/2011 9:39:23 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot final ok
ELE11-00265 Electrical Rough-In5/19/20115/20/20115/20/2011 9:24:42 AMAPASS
Need a canopy inspection and also a drop ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Tina Payne rough-in ok cover drop ceilings/ outside canopy
ELE11-01009 Conference5/19/20115/20/20115/20/2011 9:14:56 AMADONE
call before//Rob Starr Phone #: ###-#### Solar photovoltaic pole lighting fixtures
ELE10-02365 Final5/19/20115/20/20115/20/2011 8:53:12 AMAPASS
Call me ahead for access. Phone #: ###-#### >> Inspection requested via web by Cevyn Recla final ok
ELE11-00327 Final5/19/20115/20/20115/20/2011 8:23:42 AMAPASS
Steve Phone #: ###-#### >> Inspection requested via web by steve cooper final ok
ELE11-00349 Final5/19/20115/20/20115/19/2011 2:03:07 PMAPASS
Daryl, thank you. Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe final ok