Inspections for the day of: Monday, May 20, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00020 INSP-Conference5/20/20135/20/20135/20/2013 3:45:21 PMPDONE
Frank and I discussed the relocation of the electric alarm bells to the nearest point ot the building to the street. Per Potter Electric the bell must be mounted vertical with the weather proof back boxes (per NEC).
FIR13-00195 INSP-Sprinkler Rough-in5/20/20135/20/20135/20/2013 3:40:58 PMPPASS
Rough-in passed. Piping can be covered.
FIR12-00693 INSP-Conference5/20/20135/20/20135/20/2013 3:37:28 PMPDONE
Frank and I discussed the relocation of the electric alarm bells to the nearest point ot the building to the street. Per Potter Electric the bell must be mounted vertical with the weather proof back boxes (per NEC).
FIR13-00070 INSP-Final Inspection5/20/20135/20/20135/20/2013 3:34:20 PMPPASS
Permit finaled. Forward flush passed.
FIR12-00260 INSP-Final Inspection5/20/20135/20/20135/20/2013 2:51:45 PMAPART
Temporary occupancy approved by building official per approval of plan modifications. The applicant has requested a TCO due to the addition not being completed. The estimated completeion date of the addition is within 360 days or sooner per the applicant.
BLD12-01449 FIRE-Final Inspection5/20/20135/20/20135/20/2013 2:50:37 PMPPART
Temporary occupancy (life safety) approved by building official per approval of plan modifications. The applicant has requested a TCO due to the addition not being completed. The estimated completeion date of the addition is within 360 days or sooner per the applicant.
BLD12-03157 FIRE-Final Inspection5/17/20135/20/20135/20/2013 2:02:02 PMAFAIL
Life safety will be ok to pass when the project related fire alarm permit is finaled.
FIR13-00168 INSP-Final Inspection5/17/20135/20/20135/20/2013 2:00:06 PMAFAIL
All devices tested ok but internet tech. is being used for the central station communication. The approved plans indicate two phone lines. Plan reviewer approval is needed for this. A plan modification may be required.
BLD13-01192 FIRE-Final Inspection5/17/20135/20/20135/20/2013 1:48:32 PMPFAIL
Provide sticker at the main exit, provide single action hardware for all other doors as per the reviewer comments or get plan review approval for deleting doors.
BLD12-01772 FIRE-Final Inspection5/16/20135/20/20135/20/2013 10:41:59 AMAPART
A temporary for the life safety is approved for the east half of the building per letter from Jason.