BLD13-00059 FIRE-Final Inspection5/19/20145/20/20145/20/2014 1:20:50 PMPPASS
life safety passed
FIR13-00682 INSP-Final Inspection5/16/20145/20/20145/20/2014 11:38:53 AMAFAIL
See the city approved plans for locations and types of corrections needed. They include the need for addirional audio/visual devices and atleast one new smoke detector. Several wall mounted smoke detectors need relocated closer to the ceiling. As-builts are needed as well as the testing of the elevator recall, EOL's and fire sprinkler devices.
BLD14-01212 FIRE-Final Inspection5/19/20145/20/20145/20/2014 10:30:12 AMAPASS
Life safety passed