BLD14-03259
| FIRE-Conference | 5/19/2015 | 5/20/2015 | 5/21/2015 1:40:20 PM | A | PASS |
|
|
Discussed fire life safety items with contractor.
|
BLD14-03318
| FIRE-Final Inspection | 5/19/2015 | 5/20/2015 | 5/21/2015 11:20:54 AM | A | PASS |
|
|
Life safety passed.
|
FIR15-00227
| INSP-Final Inspection | 5/20/2015 | 5/20/2015 | 5/20/2015 3:43:35 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR14-00783
| INSP-Sprinkler Rough-in/Hydro | 5/19/2015 | 5/20/2015 | 5/20/2015 3:32:18 PM | A | PASS |
|
|
The underground hydro from the United Water outlet to the first coupling above the floor is passed.
|
FIR15-00327
| INSP-Final Inspection | 5/19/2015 | 5/20/2015 | 5/20/2015 3:27:43 PM | A | CANC |
|
|
Jed stated he needed to find the plans.
|
FIR15-00247
| INSP-Final Inspection | 5/20/2015 | 5/20/2015 | 5/20/2015 2:56:26 PM | P | CANC |
|
|
To be rescheduled for next week per contractor
|
FIR14-00910
| INSP-Final Inspection | 5/19/2015 | 5/20/2015 | 5/20/2015 2:54:53 PM | A | CANC |
|
|
Project related fire alarm permit not called in for inspection.
|
FIR15-00064
| INSP-Alarm Testing | 5/19/2015 | 5/20/2015 | 5/20/2015 2:05:14 PM | A | CANC |
|
|
Ken and I agreed to reshedule for tomorrow morning at 7:00am
|
BLD15-01375
| FIRE-Conference | 5/20/2015 | 5/20/2015 | 5/20/2015 2:04:01 PM | P | DONE |
|
|
The general contractor and I discussed exit signs and emergency light placement. Exit signs need to be placed as shown on the approved plans. I marked one additional exit sign to be added to clarify exiting. Per contractor emergency lighting will be added through-out with the new lighting. I will need emergency lighting in the existing core/elevator lobby
|
FIR14-00758
| INSP-Sprinkler Rough-in | 5/19/2015 | 5/20/2015 | 5/20/2015 10:33:33 AM | A | PASS |
|
|
Rough-in and tenting inspection passed. Piping can be covered.
|
BLD15-01038
| FIRE-Final Inspection | 5/19/2015 | 5/20/2015 | 5/20/2015 9:55:41 AM | A | PASS |
|
|
life safety passed
|
FIR15-00247
| INSP-Alarm Testing | 5/20/2015 | 5/20/2015 | 5/20/2015 9:23:43 AM | A | FAIL |
|
|
No city approved plans on site. However I agreed to due/view a functional test of the two speaker strobes.
|
FIR15-00002
| INSP-Sprinkler Rough-in/Hydro | 5/19/2015 | 5/20/2015 | 5/20/2015 8:33:30 AM | P | FAIL |
|
|
Inspection today was for the basement and second floor rough-in and hydro tests. Hydro tests failed due to test pump and the need to modify the system. See the city approved plans for location and corrections needed which include overspaced heads, missing branchline restraints, missing flexible cplgs and missing coverage. Ball drip is installed in wrong side of check valve. Plans need to be resubmitted showing the pipin routing changes including riser nipples, additional piping heads and elevation changes.
|