ELE02-00650
| Final | 5/20/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | A | PASS |
|
|
###-#### CODE # 0566
|
ELE02-01504
| Electrical Rough-In | 5/20/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | A | PART |
|
|
MARK ###-#### CELL ###-####
conf and partial U/G ok 5/21/2002 11:00:45 AM
|
ELE02-01291
| Electrical Rough-In | 5/20/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 05/20/2002 at 10:24:15. Contact: ###-####.
U/G Ok 5/21/2002 12:52:00 PM
|
ELE02-00204
| Electrical Rough-In | 5/20/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | A | PASS |
|
|
trench insp- tim- ###-#### U/G to garage ok 5/21/2002 12:02:22 PM
|
ELE01-02785
| Final | 5/20/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | P | FAIL |
|
|
fn -jim ###-####
derate wires in large conduit feeding relays
and GFCI protection of recep in garage and elevator room 5/21/2002 3:34:05 PM
|
ELE02-01517
| Electrical Rough-In | 5/21/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | P | FAIL |
|
|
LLOYD ###-####
Protect MC cable 5/21/2002 9:45:03 PM
|
ELE02-00423
| Electrical Rough-In | 5/21/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | P | FAIL |
|
|
###-#### ceiling cover
Open boxes without grounding pigtails and no support of MC within 12 in. of box 5/21/2002 3:32:05 PM
|
ELE02-01520
| Electrical Rough-In | 5/21/2002 | 5/21/2002 | 5/21/2002 12:00:00 AM | P | CANC |
|
|
r/i mike ###-#### -call 1/2 hr before insp if possible
Not ready 5/21/2002 4:44:22 PM
|